How to connect to 2-pole breaker
(1) When "N" is marked on the breaker,connect the N phase wire as marked. (2) When "N" is not marked on the breaker, N phase wire can be connected to eith... More Details >>
degrees of protection to IEC60529
The degess of protection for ACB is IP20 as standard (under the condition that front door is closed). For MCCB and ELCB, the degrees of protection can be IP2... More Details >>
3P MCCB in 1-phase 2-wire circuit
It is possible. Refer to the figure for connection as below. More Details >>
MCCB, ELCB and ACB at higher altitudes
In that case, the rated current and the rated voltage shall be reduced. Refer to the table of derating factors as below. More Details >>
It is a button in order to trip MCCB. It is used for regular inspection of the switching mechanism, and trip condition of MCCB when Alarm switch (AL) and Shu... More Details >>
Default setting of electronic breakers
Each setting knob of the overcurrent trip characteristic is set to the maximum value and then shipped if not specified. However, only the pre-alarm is set to... More Details >>
It is the number that can be opened/closed per hour under the conditions specified in the standard. More Details >>
Storage temperature range of MCCBs an...
It is from -25 to 55℃ in Trip or OFF position. However, it shall be in an environment without condensation and freezing even in a short time. More Details >>
Change Electronic relay characteristi...
Only electricians who have enough technical knowledge should change the setting of overcurrent tripping and earth leakage tripping characteristics. Moreover,... More Details >>
It is possible to attach closely if there is no problem about the insulation distance between live parts such as a terminal bar and load currents are 80% or ... More Details >>