The time between application of voltage to the closing coil (CC) and closing of the main contact is 0.08 sec or less. More Details >>
- No:22440
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Generally, there is no Mechanical Trip indication of continuous output for AE-SW. It is necessary to indicate electrically by using OCR Alarm (AL) output or ... More Details >>
- No:22432
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
High inst MCCB for transformer primary side
It is a circuit breaker which has higher instantaneous tripping current value in order to prevent unwanted tripping by magnetizing inrush current of a transf... More Details >>
- No:22358
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
It is special relay characteristic for selective co-ordination. When closing ACB (changing from OFF to ON), the instantaneous tripping characteristic is effe... More Details >>
- No:22402
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
The test position is a position where a main circuit is in the "disconnected" state and only control circuit is in the "connected" state. Control circuit che... More Details >>
- No:22405
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
For Shunt Trip (SHT), it is the time from voltage application to open ACB main contact * AE3200-SW or less, AE4000-SWA: 0.04 sec or less* AE4000-SW to AE6300... More Details >>
- No:22418
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
ELCB Default setting Time-delay type sensitivity
Both of the adjustment knob is set to the maximum value when shipping in order to prevent unwanted earth leakage tripping when Earth Leakage Circuit Breaker ... More Details >>
- No:22388
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
A shunt trip (SHT) is an internal accessory which electrically and remotely trips a circuit breaker. When the supply voltage of the SHT is remained between 7... More Details >>
- No:22342
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
It is possible to use it if you connect with right and left poles, not neutral pole. Since electronic circuit power supply for earth leakage detection is tak... More Details >>
- No:22359
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Almost MCCBs can be connected n reverse. Check the item column of specification table "reverse connection" in the catalog. If it says "Possible", MCCB can be... More Details >>
- No:22442
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers