FAQ within [ Low-voltage Circuit Breakers ]
-
It may not trip a fault current or degrade insulation after tripping. When you connect the device in reverse, you must select a reverse-connectable model. More Details >>
- No:22345
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Type name of the operating handle
F-2SV is standard, F-2SVE is for emergency use. The difference is the color of the handle and its surroundings parts. More Details >>
- No:38028
- Release Date:2021/01/22 17:37
- Category: Accessories and Related Components
-
Calorific value of the circuit breaker
1. The internal resistance (per pole) is described in the catalog and technical notes. 2. Power consumption (W) = RI^2 x Poles = Resistance (Ω) x Load curre... More Details >>
- No:38025
- Release Date:2021/01/22 17:39
- Category: Molded Case Circuit Breakers
-
Bar terminal material for 400A is aluminum alloy, and for 630A or higher is copper. More Details >>
- No:24819
- Release Date:2019/04/09 15:13
- Category: Molded Case Circuit Breakers
-
lower limit of operational voltage for DC
It is DC 24V. More Details >>
- No:24816
- Release Date:2019/04/09 15:17
- Category: Molded Case Circuit Breakers
-
It is a button in order to trip MCCB. It is used for regular inspection of the switching mechanism, and trip condition of MCCB when Alarm switch (AL) and Shu... More Details >>
- No:22444
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Release element in neutral (4P breaker)
AE-SW 4-poles with WS relay (general protection) has overcurrent protection for neutral-pole. The tripping characteristic is same as phase-pole. Moreover, A... More Details >>
- No:22441
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
The applicable voltage is 440V or less. Moreover, High-speed type can be used from 85 to 484V, and Time-delay type can be used from 170 to 484V. More Details >>
- No:22421
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
ACB combination Ground fault protection and earth leakage protection
It is not possible to combine them at the same time. You need to choose one of them. More Details >>
- No:22419
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Insulating barrier in the package
Use the insulation barrier if they are packed with. If not using that, breaking performance is not guaranteed. For models that the insulation barrier is not ... More Details >>