FAQ


FAQAbout Products

- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-F Series
FAQ
Keyword Search
FAQ within [ MELSEC-F Series ]
-
Clock function accuracy of the MELSEC-F series
The accuracy is within ±45 seconds/month (ambient temperature: 25ºC). More Details >>
- No:24778
- Release Date:2019/02/27 15:57
- Category: MELSEC-F Series , Main Unit
-
Operation of the first special function unit/block in the FX3UC series
Usually, unit number of the first special function unit/block is "K0". However, when the main unit is FX3UC-32MT-LT(-LT2), the unit number "K0" is assigned t... More Details >>
- No:24995
- Release Date:2019/04/23 10:40
- Category: MELSEC-F Series , Main Unit
-
Pulse output type of the FX3U-1PG pulse output block
It is transistor output. Transistor output specifications are as follows. ・ Rated load voltage 5 to 24 V DC ・ Maximum load current 20 mA or lower More Details >>
- No:24972
- Release Date:2019/04/23 07:19
- Category: MELSEC-F Series , Positioning Control
-
Yes, it is possible. To set the programmable controller to RUN again, while the programmable controller is stopped, set the built-in RUN/STOP switch as follo... More Details >>
- No:24965
- Release Date:2019/04/23 07:18
- Category: MELSEC-F Series , Main Unit
-
FX series with a built-in USB port
The FX3S,FX3G/FX3GC series hasa built-in USB port. More Details >>
- No:24937
- Release Date:2019/04/18 14:24
- Update:2023/01/31 11:59
- Category: MELSEC-F Series , Main Unit
-
MELSOFT connection of the FX3U-ENET-ADP Ethernet communication special adapter
Up to 4 connections can be opened. More Details >>
- No:24903
- Release Date:2019/04/15 11:31
- Category: MELSEC-F Series , Network/Communication
-
Connection of FX-20P and FX3U series
Whenan entry code (2nd entry code) registration is set in the FX3U series, sucherror canoccur. More Details >>
- No:24983
- Release Date:2019/04/23 07:21
- Category: MELSEC-F Series , Accessories
-
Maximum length of input wiring
Although it depends on the operating environment, wiring within 20 m is generally recommended. More Details >>
- No:24949
- Release Date:2019/04/18 14:29
- Category: Main Unit
-
It takes 1 ms or less in a unit of the motor system and 2 ms or less in a unit of the machine system. * Motor system∙∙∙The pulse number is used as the stand... More Details >>
- No:24943
- Release Date:2019/04/18 14:25
- Category: MELSEC-F Series , Positioning Control
-
Terminal blocks for the MELSEC-F series
Whether the terminal block is removable or not differs depending on the series. Types of the terminal blocks for the MELSEC-F series main units are as follow... More Details >>
- No:24774
- Release Date:2019/02/27 15:34
- Category: MELSEC-F Series , Main Unit
181-190 of Total 198