FAQ
FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-F Series
FAQ
Keyword Search
FAQ within [ MELSEC-F Series ]
-
Yes, there is. T256 to T319 can be used for the1 ms timer, and T246 to T249 can be used for the 1 ms retentive timer. More Details >>
- No:24680
- Release Date:2019/02/22 11:39
- Update:2019/02/22 14:03
- Category: MELSEC-F Series , Main Unit
-
How to change the keeping (latched device data) range (FX3G/FX3GC)
The keeping (latched device data) range is fixed and cannot be changed in parameters. (Reference) [When an optional battery is not used] The keeping ran... More Details >>
- No:22260
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:52
- Category: MELSEC-F Series , Engineering Software , Main Unit , Accessories
-
Battery replacement during power-on
Replacethe battery when the programmable controller is powered off. For example, forthe FX3U/FX3UC series, data will be held for about 20 seconds after be... More Details >>
- No:22257
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:54
- Category: MELSEC-F Series , Main Unit , Accessories
-
The station number setting is not required for non-protocol communication. More Details >>
- No:24948
- Release Date:2019/04/18 14:27
- Category: MELSEC-F Series , Main Unit , Network/Communication
-
Connecting a USB interface of a personal computer to a programmable controller
・ The FX-USB-AW can be used for the programmable controllers except for the FX3S/FX3G/FX3GC series. ・ Since the FX3S/FX3G/FX3GC series have the built-in USB... More Details >>
- No:24707
- Release Date:2019/02/27 09:00
- Category: MELSEC-F Series
-
Thecomment may not have been written tothe programmable controller. Or, the comment display setting may be required on the GX Works2 side. [Writing a com... More Details >>
- No:24681
- Release Date:2019/02/22 11:40
- Update:2019/02/22 14:15
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
M384 to M1535 and D128 to D1099 can be latched. M1536 to M7679, D1100 to D7999, and R0 to R23999 can be used as latch areas by installing an optional batt... More Details >>
- No:24703
- Release Date:2019/02/27 08:59
- Category: MELSEC-F Series , Engineering Software , Main Unit , Accessories
-
How to check the scan time (MELSEC-F series)
The present scan time is stored in D8010. Monitor the valueusing a programming tool such as GX Works2 and GX Developer. More Details >>
- No:24685
- Release Date:2019/02/22 11:40
- Update:2019/02/22 15:07
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
The FX3U-ENET-ADP does not support the DHCP function. Set the fixed IP address using the parameter setting of GX Works2. On GX Works2, select "Parameter" and... More Details >>
- No:24870
- Release Date:2019/04/15 08:05
- Category: MELSEC-F Series , Network/Communication
-
I/O structure error in the MELSEC-F
When an unimplemented input (X) or output (Y) number is used in a program, M8060 turns on. The first to third digits of the numericalvalue stored in D8060 i... More Details >>
- No:22284
- Release Date:2018/08/30 13:48
- Update:2019/02/18 15:17
- Category: MELSEC-F Series , Engineering Software , Main Unit
11-20 of Total 198