Programming software and tool for the FX2N-10GM/FX2N-20GM
Use the "FX-PCS-VPS/WIN" software for personal computer or the "E-20TP-SET0" handy programming panel. More Details >>
- No:25014
- Release Date:2019/04/23 11:16
- Category: MELSEC-F Series , Engineering Software , Accessories
-
Setting day of the week when using the TWR instruction (FX3 series)
Day of week is automatically set. When data written to the data register for storing day-of-the-week data is within the setting range (K = 0 to 6), the day ... More Details >>
- No:24777
- Release Date:2019/02/27 15:57
- Category: MELSEC-F Series , Main Unit
-
Counting of a built-in high-speed counter
Check that the RST instruction ofthe high-speed counter is not executed whilethe program is running. Forthe high-speed counter which supports the external r... More Details >>
- No:24787
- Release Date:2019/02/28 09:06
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Special auxiliary relay which is always on (MELSEC-F)
M8000 More Details >>
- No:22258
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Turning on a bit in the data register
In the FX3U/FX3UC series, the bit specification of the data register is possible. (Example) D0.7→7th bit in D0 For the other types of MELSEC-F programmable... More Details >>
- No:22275
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
How to change the keeping (latched device data) range (FX3G/FX3GC)
The keeping (latched device data) range is fixed and cannot be changed in parameters. (Reference) [When an optional battery is not used] The keeping ran... More Details >>
- No:22260
- Release Date:2018/08/30 13:48
- Update:2019/02/19 11:52
- Category: MELSEC-F Series , Engineering Software , Main Unit , Accessories
-
Protection components of relay contacts
We recommend you to connecta diode for commutation to the DC load, and surge absorber (C-R) to the AC load for the protection of the relay contacts. More Details >>
- No:24999
- Release Date:2019/04/23 10:39
- Category: MELSEC-F Series , Main Unit
-
When a personal computer (GX Works2) is connected to the RS-232C port of a programmable controller, communications between the personal computer and the prog... More Details >>
- No:24782
- Release Date:2019/02/27 16:10
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Thecomment may not have been written tothe programmable controller. Or, the comment display setting may be required on the GX Works2 side. [Writing a com... More Details >>
- No:24681
- Release Date:2019/02/22 11:40
- Update:2019/02/22 14:15
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
Periodic replacement is recommended. For example, standard life of FX3U-32BL is 5 years (at ambient temperature of 25). The life of the battery changes wit... More Details >>
- No:22262
- Release Date:2018/08/30 13:48
- Category: MELSEC-F Series , Main Unit , Accessories