Low-voltage Power Distribution Products
FAQ within [ Low-voltage Power Distribution Products ]
-
Set values cannot be changed on the setting mode (ME96SS series).
When[SET] is flashing, the “Setting Value Confirmation Mode” is selected. In this case, the set values cannot be changed. Pressing the buttons of the “Set” ... More Details >>
- No:22168
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:22
- Category: Electrical Indicators
-
Inverse time delay operating characteristic
It is a characteristic that operating time inversely become shorter as current increases. For Molded Case Circuit Breakers, protection characteristic meeting... More Details >>
- No:22387
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
High inst MCCB for transformer primary side
It is a circuit breaker which has higher instantaneous tripping current value in order to prevent unwanted tripping by magnetizing inrush current of a transf... More Details >>
- No:22358
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
It is a method which breaks short circuit current with both upstream and downstream circuit breakers. For example, in the case that short circuit current at ... More Details >>
- No:22357
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
ELCB applicable to harmonics and surge
Compared with general circuit breakers, Earth Leakage Circuit Breaker applicable to harmonics and surge has earth leakage current detecting characteristic wh... More Details >>
- No:22344
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Error in the measurement value (ME96SS series).
There is a possibility of the wiring error for VT/CT to this model. Please check the wiring for VT/CT and this model. More Details >>
- No:22179
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Availability for special primary current and special primary voltage (ME96SS series).
This model is able to be used under unusual primary current and unusual primary voltage as long as the user sets each value within the selectable range as ... More Details >>
- No:22148
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:15
- Category: Electrical Indicators
-
"b contact" is normally closed contact, and It is also called "NC (Normally Closed) contact". More Details >>
- No:22435
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
ACB combination Ground fault protection and earth leakage protection
It is not possible to combine them at the same time. You need to choose one of them. More Details >>
- No:22419
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Default setting from the factory
The knob of the sensitivity current selector is set to the maximum value when shipping in order to prevent unwanted earth leakage tripping when Earth Leakage... More Details >>
- No:22391
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers