FAQ
FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
RS-485 connection between QJ71C24N and an external device
Short between SDA and RDA and between SDB and RDB, and then connect them to + (Data-A) and - (Data-B) on the external device. More Details >>
- No:22986
- Release Date:2018/09/03 17:31
- Category: Network related products
-
CC-Link master module settings
If each master module controls their own CC-Link networks, all master modules can be set as station 0 even though they are controlled by the same CPU. More Details >>
- No:23008
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Clearing data in the QJ71C24N's receiving area buffer memory
Receiving data overwrites the buffer memory data. Writing 0 with a program can be performed but is unnecessary as the data is overwritten. More Details >>
- No:23009
- Release Date:2018/09/03 17:31
- Category: Network related products
-
MODE switch setting for QJ61BT11N
The MODE switch can set the following modes.- 0 to 4: Online mode- 5 to 9: Line test mode- A to E: Hardware test modeEach mode in ascending order of set valu... More Details >>
- No:23025
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Overall cable distance and station-to-station distance in CC-Link networks
The overall cable distance and station-to-station distance depend on the version and the transmission speed. Figure 1 shows the case with Ver.1.10-compatibl... More Details >>
- No:23028
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:14
- Category: Network related products
-
Setting required to skip CC-Link slave station numbers
A CC-Link slave station number can be skipped by assigning the skipped number to a reserved station. A reserved station is counted as one of all the connecte... More Details >>
- No:23029
- Release Date:2018/09/03 17:31
- Category: Network related products
-
How to check link errors in CC-Link slave stations
The data link status is stored in SW80 to SW83.Each bit corresponds to a station number and a bit turns ON if the corresponding station causes a data link er... More Details >>
- No:23031
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Assigning X and Y signals of AJ65SBTB1-32DT
X and Y assignments are as follows.- X0 to XF- Y10 to Y1F More Details >>
- No:23034
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Difference between AJ65SBTB1-16DT and AJ65SBTB1-16DT1
Major differences in input specifications are shown below. - AJ65SBTB1-16DT - Rated input current approx. 7 mA - ON voltage/ON current 14 VDC or higher/... More Details >>
- No:23035
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:24
- Category: Network related products
-
Duplication error in a CC-Link master station
Possible causes are as follows.(1) Another master station exists on the same line.(2) Noise is detected on the line at power on. More Details >>
- No:23044
- Release Date:2018/09/03 17:31
- Category: Network related products
451-460 of Total 1055