Fault output signal when inverter trips
Only the unit type SC-A□□U has fault output signals. (Terminals Y1 and SD open collector output permissible load 24 VDC 0.1 A)The box type SC-A□□B indicates ... More Details >>
- No:21580
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , SC-A
-
To almost "1". (With load factor of 100%) More Details >>
- No:21577
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Options
-
Accessories and inverter with built-in high power factor converter
If the reactor 1, outside box, and reactor 2 are contained in the same case as the high power factor converter, the unit becomes larger and heavier while fre... More Details >>
- No:21573
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Options
-
Faults history upon power failure
When an instantaneous power failure of 100 msec or longer occurs, the inverter is reset* and it is not recognized as a fault. Since it is not recognized as a... More Details >>
- No:21551
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
If you connect two frequency setting potentiometers to the terminals 5 and 10, the permissible current of 10 mA is exceeded, and you need to install 2 KΩ res... More Details >>
- No:21494
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Wire length between inverter and motor
1. Wiring length between the inverter and the motor should be 500 m or less. For 0.75 kW or lower motors, the following relationship is true: Capacity... More Details >>
- No:21392
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL
-
After inputting the start signal performing the tuning, output the output frequency. The tuning ends in approximately 500 ms in maximum after started. Durin... More Details >>
- No:21372
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
The USB connection requires FR Configurator (FR-SW3-SETUP-WJ) prepared by Mitsubishi Electric Corporation. More Details >>
- No:21318
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700
-
Noise effect of CC-Link IE communication
The same test as CC-Link is performed, and we confirmed no problem. More Details >>
- No:21226
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
The acceleration time is 60 Hz and 5 seconds, and deceleration time is 60 Hz and 60 seconds. More Details >>
- No:21166
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
1181-1190 of Total 1353