FAQ within [ Drive Products ]
-
Real sensorless vector control
No, Real sensorless vector control cannot be used in the FR-E700. More Details >>
- No:21269
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700
-
Pr.38 of the E500 corresponds to Pr.125 (Terminal 2 frequency setting gain frequency) of D700. Pr.39 of the E500 corresponds to Pr.126 (Terminal 4 frequency ... More Details >>
- No:21254
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-D700
-
They are insulated. More Details >>
- No:21242
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Earthing (grounding) of FR-A7NC (E kit)
There is no problem, however, earthing (grounding) from each FG terminal is recommended to avoid the influence of noises. More Details >>
- No:21240
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Remote input signal of CC-Link communication
When the communication error occurs, the input signal status is not retained, and all the bits turn OFF. When the communication establishes again, the bit tu... More Details >>
- No:21237
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Monitor value at CC-Link communication
The data of output frequency, output current, and output voltage are retained at alarm occurrence, but other monitors are not. More Details >>
- No:21235
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
It is tilted to wire the cable easily. More Details >>
- No:21228
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
System environment variable of the Modbus-RTU communication
They are not received during the operation. They are also not received if the command authority does not exist in the communication. When they are executed i... More Details >>
- No:21223
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
LED blinking under encoder feedback control
The Z-phase signal may be connected to the A-phase or B-phase incorrectly. Check the wiring. More Details >>
- No:21220
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
LED blinking under encoder feedback control
The following may be the cause. - No encoder power supply. - The setting of Pr.359 (Encoder rotation direction) is reversed. - The signal from the encoder is... More Details >>
- No:21219
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
1201-1210 of Total 1368