FAQ within [ Drive Products ]
-
The error indicates that the parameter setting of the PLC function is not set. It is considered that the PC parameter is not checked when the PC parameter an... More Details >>
- No:20859
- Release Date:2018/08/22 16:24
- Category: FREQROL-A800 , FREQROL-F800
-
When connecting to the P/+, the current flows in the inrush circuit at the regenerative driving. This regenerative current may generate losses in the inrush ... More Details >>
- No:20815
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL
-
Instruction manual of capacity selection software
You can download the instruction manual from the Mitsubishi Electric FA Global Website. Visit the Mitsubishi Electric FA Global Website and go to [Download]... More Details >>
- No:23643
- Release Date:2018/09/14 15:10
- Category: Servo Support Software
-
Servo motor does not rotate when the command pulse is input.
The pulse train form outputted with the controller and the setting of servo amplifier (command pulse input form) may differ. Check the parameter settings. (M... More Details >>
- No:23631
- Release Date:2018/09/14 15:10
- Category: MELSERVO-J4 , MELSERVO-JE , MELSERVO-JN , MELSERVO-J3 , MELSERVO Others
-
The filtering effect is higher as the cable is wound more.However, if the cable is wound more than 4T on the inverter output side, since the inverter's outpu... More Details >>
- No:22064
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
Frequency does not rise with blower
Our suggestion is to adjust the following parameters:1. Set Pr.14 = 0. If the V/F pattern for variable-torque load (Pr.14 = 1) is used, the current may incre... More Details >>
- No:22060
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-F500
-
Inverter's heat generation quantity
The heat generation quantity while the inverter is outputting the rated current is as follows:1. FR-A520-3.7K: 230 W2. FR-A520-7.5K: 420WThe heat generation ... More Details >>
- No:22057
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
As an example, you can use an inverter to feed the cord at the constant speed under dancer control using a combination of the deviation detector and deviatio... More Details >>
- No:22047
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Installation clearance of inverters
Keep 1 cm or more of clearance for 3.7 K or smaller, and 5 cm or more for 5.5 K or larger.If the clearance is too small, the cooling effect is lowered. Secur... More Details >>
- No:22046
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Installing parameter unit outside control panel
You can install the operation panel FR-DU04 (or parameter unit FR-PU04) on the enclosure surface by connecting it with the inverter via a cable.To do this, d... More Details >>
- No:22044
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
161-170 of Total 1368