FAQ


FAQAbout Products
FAQ
Keyword Search
Drive Products
-
FREQROL-A800(142)
FREQROL-F800(89)
FREQROL-A700(351)
FREQROL-D700(260)
FREQROL-E700(393)
FREQROL-F700(295)
FREQROL-F700P(294)
FREQROL-F700PJ(251)
FREQROL-A024(40)
FREQROL-A100(21)
FREQROL-A200(32)
FREQROL-A500(119)
FREQROL-B(9)
FREQROL-E500(84)
FREQROL-F400(2)
FREQROL-F500(15)
FREQROL-S500(11)
FREQROL-U100(16)
FREQROL-V200(51)
FREQROL-Z020(1)
FREQROL-Z024(2)
FREQROL-Z100(2)
FREQROL-Z123(2)
FREQROL-Z200(3)
FREQROL-Z300(2)
SC-A(12)
Engineering Software(41)
Magnet motor drive(9)
Peripheral devices(7)
Options(127)
Plug-in Options(30)
Others(53)
FAQ within [ Drive Products ]
-
No, it cannot be normally closed contact. When the electronic bypass function is used, the setting of Pr.17 is disabled. More Details >>
- No:21193
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
FR Configurator (English version)
The English version cannot be updated from the Website. FR-SW3-SETUP-WE needs to be purchased. More Details >>
- No:21195
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
There is no regulation value. Use the inverters in the environment without corrosive gas. More Details >>
- No:21201
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Monitor value at CC-Link communication
The data of output frequency, output current, and output voltage are retained at alarm occurrence, but other monitors are not. More Details >>
- No:21235
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Countermeasures when input power supply is turned off upon equipment fault
1. When the inverter power supply is turned OFF, the inverter is disconnected from the CC-Link network. However, since the CC-Link master station has the aut... More Details >>
- No:21390
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
Installing reactor for suppressing harmonics
You can connect multiple inverters to a single reactor. In this case, the load seems to be light from the reactor unless all of the inverters are rotating an... More Details >>
- No:21410
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Options
-
There is a 10 ms delay after the inverter recognizes the start command (STF OR STR) before it starts decelerating. The delay is 10 ms. A delay of 100 ms is i... More Details >>
- No:21445
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Inverter with one-rank higher capacity
An inverter with one-rank higher capacity is often used when a high torque is required for a short period of time. (Examples)- When rapid acceleration/decele... More Details >>
- No:21456
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL
-
Compatibility with Y-△ motor and others
1. You can connect them using △ connection. 2. No problem with connecting four Y-△ motors. (Connect all four motors using △ connection.) (Note that the inver... More Details >>
- No:21487
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Others
-
The inverter efficiency (power factor) for the inverter alone is approximately 75 to 80%. However, by installing the power factor improving DC reactor to the... More Details >>
- No:21512
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A100
381-390 of Total 1353