FAQ within [ Drive Products ]
-
System environment variable of the Modbus-RTU communication
It decelerates and stops. The operation is the same as the one when the Bit of forward rotation command and reverse rotation command are turned OFF. More Details >>
- No:21222
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
FR Configurator (English version)
The English version cannot be updated from the Website. FR-SW3-SETUP-WE needs to be purchased. More Details >>
- No:21195
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Sampling time of FR Configurator2
It depends on the mask count. It is approximately 0.125 [ms] (mask count: 1) to 20 [ms] (mask count: 30). More Details >>
- No:20950
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Engineering Software
-
The resistor unit MT-BR5 manufactured in February 2016 or later has output terminal TH3 (NC contact) as a fault output terminal. More Details >>
- No:20816
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options
-
The filtering effect is higher as the cable is wound more.However, if the cable is wound more than 4T on the inverter output side, since the inverter's outpu... More Details >>
- No:22064
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
Notes when inverter capacity is larger than motor capacity
When using one-rank-higher inverter, as you mention, you need to care about the setting of the electronic thermal O/L relay.Setting the electronic thermal O/... More Details >>
- No:22040
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500
-
1. Changing frequency to 0 Hz(1) Set Pr.8 (Deceleration time) to 0 second.If the load is large, the stall prevention function may work to lengthen decelerati... More Details >>
- No:22019
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-E500
-
Set the parameters below. For other parameters, keep the initial settings.1. Set Pr.122 (Communication check time interval) to other than "0". ("9999" is OK.... More Details >>
- No:21986
- Release Date:2018/08/22 16:30
- Category: Engineering Software
-
They are capable of a load of 5 VDC±5% and 10 mA. More Details >>
- No:21977
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Surge voltage of 400 V inverter
1. Since the voltage resistance of the standard motor is not improved, it is recommended to use an "insulation-enhanced motor".If you are using an insulation... More Details >>
- No:21957
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Others