FAQ within [ Drive Products ]
-
The start commands cannot be input from both sources simultaneously because the operation command source is specified.You can switch the command source as ne... More Details >>
- No:21828
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
This is due to specifications that multi-speed selection is prioritized and setting with the setting dial is ignored.The setting dial is effective when multi... More Details >>
- No:21843
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
The way to monitor the output current and read parameters via CC-Link is identical in all operation modes. More Details >>
- No:21872
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Check if the CC-Link wires are short-circuited and/or station numbers are duplicated. More Details >>
- No:21891
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Fault contact state when input side power supply is cut off
The NC contact does not open when the power supply is cut off whether the inverter is operating or ceased.When the input side power supply is cut off, the DC... More Details >>
- No:21958
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-S500
-
Fault output terminal load pattern
The fault output terminals A and C, and B and C of the power regeneration converter FR-RC are not capable of a micro load of 5 VDC±5%, 10 mA. The minimum loa... More Details >>
- No:21966
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Options
-
Installation clearance of inverters
Keep 1 cm or more of clearance for 3.7 K or smaller, and 5 cm or more for 5.5 K or larger.If the clearance is too small, the cooling effect is lowered. Secur... More Details >>
- No:22046
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Yes, it can like the standard product. More Details >>
- No:20880
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
There are some restrictions compared to the FR-A800 (RS-485 communication type). For example, the FR-A8TR is unavailable, and only two option connectors are ... More Details >>
- No:20884
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
The display language of Developer is different between the Japanese version of FR Configurator2 (Ver.1.08 or later) and the English version of it (Ver.1.08 o... More Details >>
- No:20911
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Engineering Software