FAQ within [ Drive Products ]
-
It bypasses (removes) high-frequency current due to switching that is output by the FR-HC2 to prevent it from being flown into the power supply system as a f... More Details >>
- No:21152
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , Options
-
Torque control cannot be performed with the FR-E700 series. It is available with the FR-A700 and FR-V500 series. More Details >>
- No:21279
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700
-
The USB connection requires FR Configurator (FR-SW3-SETUP-WJ) prepared by Mitsubishi Electric Corporation. More Details >>
- No:21318
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700
-
Check the setting value of Pr.73. Or check Pr.C4 (Terminal 2 frequency setting gain) for the percentage of the voltage that is actually applied. For the FR-E... More Details >>
- No:21356
- Release Date:2018/08/22 16:27
- Category: FREQROL-E700
-
Using FR-A540 inverter on CC-Link
Answer to question 1 When the CC-Link option goes faulty, OPT (option error) occurs and the inverter's fault output is triggered. When communication is lost ... More Details >>
- No:21391
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
1. Choose the circuit breaker based on the inverter capacity. 2. Also, choose the brake resistor based on the inverter capacity. 3. Choose the AC reactor bas... More Details >>
- No:21425
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A024
-
It is considered to be caused by inverter PWM control. It can be suppressed by raising the PWM carrier frequency (Pr.72), but the entire noise and leakage cu... More Details >>
- No:21428
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
It is considered that communication settings between the inverter and personal computer do not match. Check if settings such as communication rate and stop b... More Details >>
- No:21431
- Release Date:2018/08/22 16:27
- Category: Engineering Software
-
When the heat sink is outside, since the heat sink and fan are not waterproof, you need to enclose them so that they are not exposed to the spray of water. More Details >>
- No:21435
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Options
-
The inverter alarm "OV3" occurs when the main circuit DC voltage inside the inverter goes higher than the preset value due to the regenerative power returned... More Details >>
- No:21438
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A024