Influence on external measurement device
It is considered that malfunction of the measurement device is due to noise. Check the noise propagation route since the countermeasure depends on it. Some c... More Details >>
- No:22100
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Others
-
With the FREQROL-U100 series, pressing and holding the [SET] switches to the current monitor. More Details >>
- No:22073
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-U100
-
Reset command during operation
The reset signal does not damage the inverter.It seems that the inverter went faulty due to other reasons.Mitsubishi Electric FA Center can inspect the inver... More Details >>
- No:22065
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Installation clearance of inverters
Keep 1 cm or more of clearance for 3.7 K or smaller, and 5 cm or more for 5.5 K or larger.If the clearance is too small, the cooling effect is lowered. Secur... More Details >>
- No:22046
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Installing parameter unit outside control panel
You can install the operation panel FR-DU04 (or parameter unit FR-PU04) on the enclosure surface by connecting it with the inverter via a cable.To do this, d... More Details >>
- No:22044
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Imbalanced input side power supply
1. Power supply voltage phase imbalance toleranceMitsubishi inverter's input power supply voltage phase imbalance tolerance is ±3%.If the phase imbalance exc... More Details >>
- No:21987
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Fault contact state when input side power supply is cut off
The NC contact does not open when the power supply is cut off whether the inverter is operating or ceased.When the input side power supply is cut off, the DC... More Details >>
- No:21958
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-S500
-
Short-circuiting frequency setting terminals
You can short-circuit the terminals 10 and 2.If you are considering to perform operation at the maximum frequency, consider using the high-speed command RH o... More Details >>
- No:21951
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL
-
Acceleration/deceleration time
You cannot set and/or enable the acceleration time and deceleration time individually. More Details >>
- No:21938
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , SC-A
-
Class, instance, and attribute represents different grouping of objects.Comparing object grouping to a mailing address, they can be considered as follows:Sta... More Details >>
- No:21924
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-F500
741-750 of Total 1354