Encoder feedback speed accuracy
The speed variation rate is as follows: - Encoder feedback control: ±0.2% - Vector control: ±0.02% (mentioned in FR-A5AP Instruction Manual) More Details >>
- No:21422
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Plug-in Options , FREQROL-A500
-
We recommend the "YM206RI 1 mA" analog ammeter. More Details >>
- No:21402
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , Options
-
The operation panel FR-PA02 requires the optional FR-E5P (control panel rear cover and adapter set) and connection cable FR-CB20□. Check that Pr.146 (Built-i... More Details >>
- No:21367
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-F700PJ
-
No, we have no cable 50 cm long. The optional cables 1 m, 3 m, and 5 m long are available. (1 m: FR-CB201, 3 m: FR-CB203, 5 m: FR-CB205) More Details >>
- No:21365
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Advanced magnetic flux vector control
Set "13" in Pr.71. Always perform auto tuning. More Details >>
- No:21299
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700
-
When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>
- No:21284
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Yes. It is available by using the FR-A7AY (plug-in option). By setting Pr.307 (Setting for zero analog output) to "20" and Pr.309 (Analog output signal volta... More Details >>
- No:21246
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Monitor value at CC-Link communication
The data of output frequency, output current, and output voltage are retained at alarm occurrence, but other monitors are not. More Details >>
- No:21235
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
System environment variable of the Modbus-RTU communication
It decelerates and stops. The operation is the same as the one when the Bit of forward rotation command and reverse rotation command are turned OFF. More Details >>
- No:21222
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
No, it cannot be normally closed contact. When the electronic bypass function is used, the setting of Pr.17 is disabled. More Details >>
- No:21193
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P