FAQ within [ Drive Products ]
-
Pr.133 can be written.Since the data code numbers of parameters are duplicate, target parameters are switched by link parameter extended setting.You can acce... More Details >>
- No:21976
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , Plug-in Options , FREQROL-A500 , FREQROL-F500
-
The following is the case for the FREQROL-A500 series:1. When the R phase or S phase is lost, the inverter stops since it loses the control power supply.2. W... More Details >>
- No:22010
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Not required. Select it according to the capacity of the vector motor used. More Details >>
- No:20804
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , Options
-
There are some restrictions compared to the FR-A800 (RS-485 communication type). For example, the FR-A8TR is unavailable, and only two option connectors are ... More Details >>
- No:20884
- Release Date:2018/08/22 16:24
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
Communication specifications for connection of multiple inverters
Use the RS485 terminal for the multiple communication of the A series/F series inverters.* Communication with the PU connector is only one-to-one connection. More Details >>
- No:20998
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , FREQROL-A800 , FREQROL-F800
-
No, it does not run. "Err" is displayed when it is operated. Always input the same voltage (400 V) to the main power supply and control power supply. More Details >>
- No:21179
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Operation under torque limit in the speed control mode
Under a 50% torque limit, if the commanded speed (50 Hz in your example) cannot be achieved without torque exceeding 50%, since the torque does not exceed th... More Details >>
- No:21483
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-V200
-
Acquisition of pressure-resistant explosion-proof certification
The test institutes assigned by the Minister of Health, Labour and Welfare (National Institute of Occupational Safety and Health and Technology Institution o... More Details >>
- No:21510
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Others , FREQROL-B
-
You can check the fault records with Pr.544 (CC-Link extended setting) set to "12" for double setting.Set H74 for the instruction code and turn ON RYF. More Details >>
- No:21829
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Slow blinking of the RUN LED indicates reverse operation.Fast blinking indicates that while the start command is input, the running frequency command is not ... More Details >>
- No:21833
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P