Pr.38 of the E500 corresponds to Pr.125 (Terminal 2 frequency setting gain frequency) of D700. Pr.39 of the E500 corresponds to Pr.126 (Terminal 4 frequency ... More Details >>
- No:21254
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-D700
-
Proportional band of multiple inverters
By importing the operation frequency from the AM terminal (analog output) of the first inverter to the FR-FH (ratio setter), the operation command which is p... More Details >>
- No:21250
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Use the FR-A740. Basically, select the capacity according to the calculation result of "rated inverter output current ? rated motor current × 1.1". More Details >>
- No:21244
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P
-
Dancer control during CC-Link communication
It is not possible under the dancer control. When the negative data is written, it is handled as the positive data in operation. Example) When Pr.541 is set ... More Details >>
- No:21243
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Remote register when instruction code execution request is issued at CC-Link communication
The value "0" is stored. More Details >>
- No:21234
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
PID control of CC-Link communication
When performing the PID control by CC-Link communication, the X14 signal is disabled. More Details >>
- No:21233
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Speed command by CC-Link communication
It is not possible when the speed command is communication. More Details >>
- No:21232
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
System environment variable of the Modbus-RTU communication
It decelerates and stops. The operation is the same as the one when the Bit of forward rotation command and reverse rotation command are turned OFF. More Details >>
- No:21222
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Communication EEPROM write selection (Pr.342)
They are cleared by the RES signal from the external terminals or inverter reset from the communication. More Details >>
- No:21221
- Release Date:2018/08/22 16:26
- Category: Inverters-FREQROL
-
Reading during the operation is possible. However, when writing is performed during the operation, "rE2" (parameter write error) occurs. More Details >>