Yes. (1) Absolute system (a) When the software stroke limit is invalid Positioning is carried out in a designated direction by "[Cd.40] ABS direction in deg... More Details >>
-
Error 3012 occurs when the multiple CPU setting of PLC CPU (CPU No.1) does not match that of Motion CPU. (1) Check if the multiple CPU setting of the Multipl... More Details >>
-
Set "[Cd.16] Inching movement amount", and turn ON the Forward run JOG start signal or the Reverse run JOG start signal. More Details >>
-
Set "[Pr.45] Home position address (72+150n, 73+150n)" of the basic parameters for home position return.Set by 2 words.The value will be reflected when PLC r... More Details >>
-
The torque limit value can be changed regardless of JOG operation status.Set the new torque limit value with "[Cd.22] New torque value/forward new torque val... More Details >>
-
The following shows the devices for the battery errors. • [SM51] Battery low latch Turn ON when the voltage of battery reduces to less than 2.5[V]. Remains O... More Details >>
-
The following shows the setting value details.• 1 to 600: Positioning data No.• 7000 to 7004: Block start designation• 9001: Machine home position return• 90... More Details >>
-
Set "[Pr.3] Movement amount per rotation" to "36000000(360.00000degree)", and "[Pr.4] Unit magnification" to "1".The same result is obtained by setting "3600... More Details >>
-
It depends on the setting of servo parameter "[PA03] Absolute position detection system" whether the HPR request flag ("[Md.31] Status": b3) turns ON or not.... More Details >>
-
Set "[PA04] Function selection A-1" to "_1_ _h: Invalid". More Details >>