Set "[Cd.6] Restart command" to "1". More Details >>
-
Set "[Cd.17] JOG speed" before starting the operation.When changing the speed during the operation, change it to the new speed with the speed change function. More Details >>
-
How to make the expanded cyclic setting for CC-Link local stations
Make the expanded cyclic setting for a CC-Link local station using the programming tool, GX Developer or GX Works2. Follow the procedure below. (1) Set th... More Details >>
- No:23030
- Release Date:2018/09/03 17:31
- Update:2018/09/26 10:17
- Category: Network related products
-
Link register assignments in MELSECNET/10 networks
For any type of MELSECNET network (II, /10, and H), B and W devices with the same number cannot be used for multiple stations as write areas. Following th... More Details >>
- No:22971
- Release Date:2018/09/03 17:31
- Update:2018/09/25 13:24
- Category: Network related products
-
List of registers assigned to the labels set using GX Works2
To display a list of registers assigned to labels, check [Find Label Definition] and [Display all items] in the [Condition Setting] tab in the [Cross Refere... More Details >>
- No:22923
- Release Date:2018/09/03 17:30
- Update:2018/09/22 16:42
- Category: Engineering Software
-
Multiplication in the Structured Text
Basic arithmetic operations cannot be performed on unsigned words. Please assign the multiplier to a signed (single/double) word. More Details >>
- No:22886
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Alive check for built-in Ethernet port LCPU
When the protocol is set to TCP, KeepAlive check is performed. (Checking for a response to KeepAlive ACK message) An alive check message is sent five seconds... More Details >>
- No:22782
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
SD1282 of LCPU with built-in Ethernet port
The bits 0 to F of the special register SD1282 (Open completion signal) correspond to the connection numbers 1 to 16. When the open processing is completed, ... More Details >>
- No:22751
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
TCP retransmission timer setting for built-in Ethernet port LCPU
For the built-in Ethernet port in the L series CPU, the TCP retransmission timer setting is fixed and unchangeable. The retransmission occurs six times. The... More Details >>
- No:22745
- Release Date:2018/09/03 17:29
- Update:2018/09/21 17:52
- Category: MELSEC-L Series
-
CPU clock setting by SNTP functions via built-in Ethernet port in LCPU
The clock setting of the CPU module is set automatically in accordance with the clock data collected from the time information server (SNTP server) on the LAN. More Details >>