FAQ
FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
M8029 (Instruction execution complete flag) is shared with multiple instructions. To obtain an execution completion result of a specific instruction, insert... More Details >>
- No:24775
- Release Date:2019/02/27 15:34
- Category: MELSEC-F Series , Network related products , Main Unit
-
Resistor value for CC-Link cables
The value depends on the type of cable in use. - Ver.1.10-compatible CC-Link dedicated cables: 110 ohm, 1/2W - CC-Link dedicated cables (Version 1.00): 110... More Details >>
- No:22983
- Release Date:2018/09/03 17:31
- Update:2018/10/03 14:42
- Category: Network related products
-
Grounding FG and LG terminals of power supply module
Both of them need to be grounded. They can be shorted and grounded as one cable. More Details >>
- No:22527
- Release Date:2018/09/03 17:28
- Category: MELSEC-Q Series
-
Latch (backup) areas in the data register (D) and extended register (R) of the FX3U/FX3UC series
D200 to D7999 and R0 to R32767 can be latched. D200 to D511 can be set as non-latch areas in parameters. For details on the parameter setting, refer to the... More Details >>
- No:24699
- Release Date:2019/02/27 08:58
- Category: MELSEC-F Series , Engineering Software , Main Unit
-
The error code "2200" is "MISSING PARA.". The causes of the error are described below. (1) The necessary parameter file does not exist in all drives. (2) ... More Details >>
- No:22749
- Release Date:2018/09/03 17:29
- Update:2018/09/22 09:12
- Category: MELSEC-L Series
-
Regarding how to format an SD memory card
In GX Works3, go to Online > CPU Memory Operation, select "SD Memory Card" and execute "Initialization." More Details >>
- No:39344
- Release Date:2023/02/15 10:03
- Category: MELSEC iQ-F Series , Option , CPU Module , Engineering Software
-
Alarm E7 (Controller forced stop warning) occurs when an forced stop is executed by the Positioning module or the Simple Motion module. The following shows h... More Details >>
-
Insufficient memory capacity for sequence programs
It cannot be increased by installing an SRAM card. The size of executable program depends on the program memory size of the CPU. Use another CPU of which p... More Details >>
- No:22578
- Release Date:2018/09/03 17:29
- Update:2018/09/20 17:09
- Category: MELSEC-Q Series
-
Inputting device comments in GX Works2
Select [Tool] -> [Options] -> [Program Editor] -> "Ladder/SFC"-> "Comment" and change "Reference/Reflection Target for Device Comment" from "Glob... More Details >>
- No:22559
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
How to check the scan time with GX Works3
You can check the processing time and scan time of the program currently being executed in "Program List Monitor". [Online] -> [Monitor] -> [Program... More Details >>
- No:22458
- Release Date:2018/09/03 17:28
- Update:2018/09/19 11:51
- Category: MELSEC iQ-R Series
31-40 of Total 1048