Regarding the FX5UC CPU module/Intelligent Function module Power Cable
The model name of the power cable is FX2NC-100MPCB. It is included with the FX5UC CPU module and intelligent function modules that require power from the pow... More Details >>
- No:40021
- Release Date:2023/08/24 14:31
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication , Motion/Positioning , Analog
-
Regarding communication with MX Component
For MX Component Ver.5, Ver. 5.000A or later supports the FX5U/FX5UC/FX5UJ CPU modules, and Ver. 5.003D or later supports the FX5S CPU module. Also, both se... More Details >>
- No:22328
- Release Date:2018/08/30 13:55
- Update:2023/02/15 13:07
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software , Network/Communication
-
Regardng compatability with other product series
Although the connection with FX2N series I/O modules, FX2 series intelligent function modules, and FX3 series special adater is not possible, FX3 series inte... More Details >>
- No:22309
- Release Date:2018/08/30 13:55
- Update:2022/12/22 09:46
- Category: MELSEC iQ-F Series , CPU Module , I/O Module
-
Regarding CW/CCW(Forward pulse/Reverse pulse) output of the built-in positioning function
FX5U/FX5UC/FX5S CPU modules are supported. Up to 2 axes are available in GX Works3 parameter settings. In addition, up to 8 axes can be added by adding a hi... More Details >>
- No:22306
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:48
- Category: MELSEC iQ-F Series , CPU Module , Motion/Positioning
-
Regarding the link refresh settings of FX5-CCL-MS
It is possible to use latch devices or I/O devices (X/Y) for link refresh devices. However, when using I/O devices (X/Y), use I/O numbers (such as X1000 ~/Y... More Details >>
- No:22308
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:37
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software , Network/Communication
-
Regarding the method to check the scan time
The current value of the scan time is stored in the following special devices. Please monitor using GX Works3. ◇Scan information SD520 Current scan time (... More Details >>
- No:22289
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:20
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software
-
Regarding the function of a special relay.
SM400 and SM8000. ※FX compatible area(SM8000~, SD8000~) is available for the special relay and special device. More Details >>
- No:22288
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:09
- Category: MELSEC iQ-F Series , CPU Module
-
Regarding EtherCAT Communications
The FX5 CPU module does not support EtherCAT communication. There are no products in the FX series or iQ-F series that support EtherCAT communication. More Details >>
- No:39313
- Release Date:2023/02/14 08:54
- Category: MELSEC iQ-F Series , CPU Module , Network/Communication
-
Regarding the built-in analog input/output function
FX5U CPU module has 2 built-in voltage input channels (DC0~10V) and 1 built-in voltage output channel (DC0~10V). If an external resister is connected, the m... More Details >>
- No:22313
- Release Date:2018/08/30 13:55
- Update:2023/06/23 10:47
- Category: MELSEC iQ-F Series , CPU Module , Analog
-
Regarding simulation function using GX Works3
For FX5U/FX5UC CPU modules, GX Works3 Ver. 1.025B or later is supported, and for FX5UJ CPU modules, GX Works3 Ver. 1.065T or later is supported. FX5S CPU mo... More Details >>
- No:22327
- Release Date:2018/08/30 13:55
- Update:2023/02/15 12:56
- Category: MELSEC iQ-F Series , CPU Module , Engineering Software