FAQ


FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Yes, there is. T256 to T319 can be used for the1 ms timer, and T246 to T249 can be used for the 1 ms retentive timer. More Details >>
- No:24680
- Release Date:2019/02/22 11:39
- Update:2019/02/22 14:03
- Category: MELSEC-F Series , Main Unit
-
Connection of the FX3G series and the GT1020/GT1030 series (5 V type)
Only one GT1020/GT1030 series (5 V type) can be connected to the FX3G series. To connect two GOTs, select the GT1020/GT1030 series (24 V type). More Details >>
- No:24969
- Release Date:2019/04/23 07:19
- Category: MELSEC-F Series , Main Unit
-
MX Component Version 3's compatibility with 64-bit Windows 7
MX Component Version 3.15R or later supports 64-bit Windows 7. More Details >>
- No:22520
- Release Date:2018/09/03 17:28
- Category: MELSEC-Q Series
-
About network parameters when building MELSECNET/10 with Q02HCPU-A
Q02(H)CPU-A is the AnUCPU equivalent. When establishing a MELSECNET/10 network, set the refresh parameter with which SB/SW data is transferred to "Y/D" or o... More Details >>
- No:23005
- Release Date:2018/09/03 17:31
- Update:2018/09/26 14:42
- Category: Network related products
-
How to check link errors in CC-Link slave stations
The data link status is stored in SW80 to SW83.Each bit corresponds to a station number and a bit turns ON if the corresponding station causes a data link er... More Details >>
- No:23031
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Duplicated coil errors that can be checked with GX Works2
When an SET instruction and RST instruction use a single device, no duplicated coil error is detected. More Details >>
- No:22932
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Cable provided with the FX2N series extension unit
It is available as a repair part. Please consult with localMitsubishi Electric representative. More Details >>
- No:24916
- Release Date:2019/04/17 11:40
- Category: MELSEC-F Series , Main Unit , I/O Extension
-
Updating to the 64-bit Windows 7 version of GX Works2
The message is displayed because the version of the CD does not support the 64-bit version. Execute the installation procedure in the condition. More Details >>
- No:22513
- Release Date:2018/09/03 17:28
- Update:2018/09/20 13:38
- Category: MELSEC-Q Series
-
QCPU built-in Ethernet port setting when using the simple PLC communication function
The following settings are required for the "Open Setting" for the number of connected external devices. - Protocol: "UDP" - Open System: "MELSOFT connecti... More Details >>
- No:22654
- Release Date:2018/09/03 17:29
- Update:2018/09/21 12:02
- Category: MELSEC-Q Series
-
How to suppress the instability of digital-converted output values
(1) Use separate cables for the AC control circuit and the external input signals of an analog input module to avoid the influence of the AC side surges an... More Details >>
- No:22709
- Release Date:2018/09/03 17:29
- Update:2018/09/21 15:11
- Category: MELSEC-Q Series
1061-1070 of Total 1123