FAQ
FAQAbout Products
FAQ
Keyword Search
Controllers
FAQ within [ Controllers ]
-
Precaution about MELSECNET/H connection (2)
- Set the network module mounted in system A to station number 0 (multiplexed remote master station). Set the network module mounted in system B to any sta... More Details >>
- No:23054
- Release Date:2018/09/03 17:31
- Update:2018/09/26 11:00
- Category: Network related products
-
Precaution about MELSECNET/H connection (1)
- Set successive station numbers for the network modules in system A and system B in a redundant system. (Station number 0 cannot be set.) - Match "host... More Details >>
- No:23055
- Release Date:2018/09/03 17:31
- Update:2018/09/26 11:12
- Category: Network related products
-
Data length for fixed buffer data communications by QJ71E71
The units of send data and receive data are shown below. - Fixed buffer data communications with the "Procedure Exist" control method: Words - Fixed buff... More Details >>
- No:23061
- Release Date:2018/09/03 17:31
- Update:2018/09/26 11:17
- Category: Network related products
-
CD terminal setting of the QJ71C24N
"The CD terminal is not checked" has been set by default. More Details >>
- No:23065
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Extending the station-to-station distance with a CC-Link IE controller
Use the optical media converter DMS-1000SL(-DC) (manufactured by Mitsubishi Electric System & Service Co., Ltd.). You can extend the station-to-station dista... More Details >>
- No:23067
- Release Date:2018/09/03 17:31
- Category: Network related products
-
Differences between the AJ65SBTB1-16TE and AJ65SBTB1B-16TE1
The following shows the major differences. -AJ65SBTB1-16TE - 1-wire terminal block, 1-common type - Maximum load current: 0.1 A/point -Protection fu... More Details >>
- No:23083
- Release Date:2018/09/03 17:31
- Update:2018/09/26 13:16
- Category: Network related products
-
No, the operation speed is not changed by changing the indirectly specified value.To change the speed during operation, use CHGV instruction. More Details >>
-
Minor error 120 occurs in the following case:The zero pass signal (M2406+20n) is OFF when the re-movement to the home position is performed by proximity dog,... More Details >>
-
Specify the target axes during operation, and execute the following speed change request instruction. (1) Motion SFC program/Motion program Speed change requ... More Details >>
-
Specify the target axes during operation, and execute the following speed change request instruction. (1) Motion SFC program/Motion program Speed change requ... More Details >>
141-150 of Total 1048