FAQ
FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
Setting day of the week when using the TWR instruction (FX3 series)
Day of week is automatically set. When data written to the data register for storing day-of-the-week data is within the setting range (K = 0 to 6), the day ... More Details >>
- No:24777
- Release Date:2019/02/27 15:57
- Category: MELSEC-F Series , Main Unit
-
Assignment of remote input device and remote output device of FX3U-16CCL-M
The remote input device and the remote output device cannot be assigned in network parameters. To assign them, create a program for updating data. For de... More Details >>
- No:24792
- Release Date:2019/02/28 09:08
- Category: MELSEC-F Series , Engineering Software , Network/Communication
-
Terminal layout of the FX3U-1PG and FX2N-1PG pulse output blocks
Yes, they have the same terminal layout. More Details >>
- No:24900
- Release Date:2019/04/15 11:30
- Category: MELSEC-F Series , Positioning Control
-
The analog input type (temperature/voltage/current) and offset/gain can be set for each channel. More Details >>
- No:24902
- Release Date:2019/04/15 11:31
- Category: MELSEC-F Series , Analog Control
-
Measurement of the counter in the MC (master control) circuit
When the count condition of the counter in the MC circuit remains set, the counter counts when the MC circuit is turned on. More Details >>
- No:24910
- Release Date:2019/04/15 11:32
- Category: MELSEC-F Series , Main Unit
-
Using a fixed latched (battery backed) type device as a general type device
Clear the required area with the ZRST instruction by using the initial pulse when the programmable controller is set to RUN. To clear all the latched type de... More Details >>
- No:24925
- Release Date:2019/04/17 11:42
- Category: MELSEC-F Series , Main Unit
-
Operation speed change during a positioning operation of the FX3U-1PG
Yes, it is possible. Write a new value to the operation speed change value (BFM#56, #55) during the positioning operation. * After the operation speed chang... More Details >>
- No:24927
- Release Date:2019/04/17 11:42
- Category: MELSEC-F Series , Positioning Control
-
Overwriting a current value with the high-speed counter comparison instruction
The output contact is activated according to the change of the current value register along with the counting input. Therefore, the value changed by executin... More Details >>
- No:24931
- Release Date:2019/04/17 11:43
- Category: MELSEC-F Series , Main Unit
-
One FX3U-ENET-ADP can be connected at the last stage (left end) of adapters for the FX3UC series. *The FX3U-ENET-ADP is a communication special adapter and ... More Details >>
- No:24932
- Release Date:2019/04/23 07:21
- Category: MELSEC-F Series , Main Unit
-
Differences between the FX3UC-32MT-LT and the FX3UC-32MT-LT2
The built-in CC-Link/LT setting differs. For the FX3UC-32MT-LT, the built-in CC-Link/LT setting is performed with the DIP switch. For the FX3UC-32MT-LT2, th... More Details >>
- No:24956
- Release Date:2019/04/18 14:28
- Category: MELSEC-F Series , Main Unit , Network/Communication
631-640 of Total 976