Yes. More Details >>
- No:22642
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
Open setting of the built-in Ethernet port QCPU
No.It is necessary to configure one port to use the MELSOFT connection. More Details >>
- No:22648
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
There are no settings for deleting the network number and PC number. More Details >>
- No:22708
- Release Date:2018/09/03 17:29
- Category: MELSEC-Q Series
-
You can use the output change upper limit value and the MV upper/lower limit limiter, the functions common to each PID control tag. Set the following parame... More Details >>
- No:22724
- Release Date:2018/09/03 17:29
- Update:2018/09/26 16:40
- Category: MELSEC-Q Series
-
QnA-compatible 3E frame command for built-in Ethernet port in LCPU
The built-in Ethernet port in the L series CPU is not compatible with a multiple-block batch read command (0406) of the MC protocol. Executable commands are ... More Details >>
- No:22726
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
Use SP.FWRITE instruction to save the data to an SD memory card in CSV format. More Details >>
- No:22727
- Release Date:2018/09/03 17:29
- Category: MELSEC-L Series
-
Connection status detection between a hub and the built-in Ethernet port of LCPU
The bit 10 of the special register SD1288 provides the connection status to a hub. When the bit 10 of SD1288 is ON, a hub is connected. More Details >>
- No:22759
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Cable length to connect to built-in Ethernet port in LCPU
The maximum length between a hub and a node is 100 m. The max. length connectable to a hub is 200m.When repeater hubs are used in cascade connection, the max... More Details >>
- No:22781
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
A message that says "A T/C coil with the same No. exists."
It is a confirmation message telling a user that there is a device, T or C, that has become a duplicated coil in the same program and the coil is given the s... More Details >>
- No:22859
- Release Date:2018/09/03 17:30
- Category: Engineering Software
-
Using GX Logviewer's realtime monitor function on multiple personal computers
Up to two realtime monitor windows can be used for monitoring.If each of two personal computers monitors one monitor window, two personal computers can be co... More Details >>