FAQ
FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
Resolution provided for L60AD4
The maximum resolution for the user range setting does not change. More Details >>
- No:22827
- Release Date:2018/09/03 17:30
- Update:2018/09/22 15:24
- Category: MELSEC-L Series
-
The conversion speed is 20 microseconds per channel. More Details >>
- No:22826
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
- Ambient temperature: 25+/-5degrees Celsius with tolerance of +/-0.1% - Ambient temperature: 0 to 55degrees Celsius with tolerance of +/-0.3% (accuracy f... More Details >>
- No:22825
- Release Date:2018/09/03 17:30
- Update:2018/09/27 11:38
- Category: MELSEC-L Series
-
Indication accuracy - Ambient temperature: 25+/-5 degrees Celsius Full scale x (+/-0.3%) - Ambient temperature: 0 to 55degrees Celsius Full scale x (+/-0... More Details >>
- No:22820
- Release Date:2018/09/03 17:30
- Update:2018/09/26 16:51
- Category: MELSEC-L Series
-
Simultaneous use of auto logging and backup functions
The auto logging function and backup function cannot be used simultaneously. The backup function must be used after the logging function is stopped. (A singl... More Details >>
- No:22819
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Use of END cover with the branch module and extension module
Use an END cover applicable to the following. - The L6EC whose serial number (first six digits) is "*****2" or later- END cover with ERR terminal (optional i... More Details >>
- No:22815
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Connected position of branch module and extension module
The position to connect the branch module and extension module is as follows. More Details >>
- No:22814
- Release Date:2018/09/03 17:30
- Update:2018/09/22 15:27
- Category: MELSEC-L Series
-
Maximum number of modules to be connected to L26CPU-(P)BT
Up to 40 modules. When the branch module and extension module are used, use L26CPU-(P)BT CPU modules whose first 5 digits of the serial number are "13072" or... More Details >>
- No:22813
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
- Ambient temperature: 25+/-5degrees Celsius with tolerance of +/-0.1% - Ambient temperature: 0 to 55degrees Celsius with tolerance of +/-0.2% (Accuracy f... More Details >>
- No:22811
- Release Date:2018/09/03 17:30
- Update:2018/09/26 16:46
- Category: MELSEC-L Series
-
I/O assignment for additional modules connected to LCPU
In L02CPU(-P), the start I/O number of the additional module begins from 10H. In L26CPU-(P)BT, the number begins from 30H. More Details >>
- No:22808
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
871-880 of Total 976