It is not grounded to the enclosure due to the resin coating. More Details >>
- No:21122
- Release Date:2018/08/22 16:26
-
Yes. However, it is difficult to wind the twisted wires because they are thick. More Details >>
- No:21128
- Release Date:2018/08/22 16:26
-
The inverter may be broken due to the temperature rise of the internal parts. More Details >>
- No:21140
- Release Date:2018/08/22 16:26
-
It controls the charging current immediately after the power is ON. (as a MC (magnetic contactor) for the charging current limit circuit, etc) More Details >>
- No:21149
- Release Date:2018/08/22 16:26
-
Since the input power factor is improved to approximately 1, the power supply capacity can be reduced to 2/3 to 3/4 of an inverter without a power factor imp... More Details >>
- No:21556
- Release Date:2018/08/22 16:28
-
A reference sine wave signal is generated inside the high power factor converter, and transistors are configured and PWM switching is performed in the conver... More Details >>
- No:21574
- Release Date:2018/08/22 16:28
-
The filtering effect is higher as the cable is wound more.However, if the cable is wound more than 4T on the inverter output side, since the inverter's outpu... More Details >>
- No:22064
- Release Date:2018/08/22 16:30
-
Because RSO (converter reset) of the HC2 is connected to RES of the inverter, the inverter is reset along with the HC2 reset. (Refer to the wiring diagram in... More Details >>
- No:20948
- Release Date:2018/08/22 16:25
-
□□□□□□ Year Month (Control number) The last digit of the manufactured year is indicated as the Year, and the Month is indicated by (A → B → C... ⇒ January → ... More Details >>
- No:20983
- Release Date:2018/08/22 16:25
-
Yes. More Details >>