FAQ within [ FREQROL-A800 ]
-
LD is not supported, however, SLD is supported. More Details >>
- No:21054
- Release Date:2018/08/22 16:25
-
If using an inverter with capacity of 75K or higher, or motor with capacity of 75 kW or higher, always select and install the inverter based on the capacity ... More Details >>
- No:21112
- Release Date:2018/08/22 16:25
-
The 800 series supports the multiple rating. Thus, the rated current of the corresponding motor is 40% or higher of the inverter rated current. (Using a moto... More Details >>
- No:21085
- Release Date:2018/08/22 16:25
-
The error indicates that the parameter setting of the PLC function is not set. It is considered that the PC parameter is not checked when the PC parameter an... More Details >>
- No:20859
- Release Date:2018/08/22 16:24
-
Europe EMC Directive compliance
By turning ON the connector of the built-in filter, the inverter can be compliant with EMC Directive (EN 61800-3 2nd Environment C3) alone. More Details >>
- No:21116
- Release Date:2018/08/22 16:26
-
Noise filter compliant with the ship classification standards
It is recommended to use the noise filter manufactured by Soshin Electric Co., Ltd. There is no difference in the filter type depending on the certification ... More Details >>
- No:21049
- Release Date:2018/08/22 16:25
-
The sine wave filter can be applied only under V/F control. When Pr.72 PWM frequency selection is set to 25, V/F control is set automatically. The applicable... More Details >>
- No:21068
- Release Date:2018/08/22 16:25
-
It is said that the EEPROM has a lifetime of 100,000 write cycles. When the data is written every time the frequency changes, the life of the EEPROM may not ... More Details >>
- No:20996
- Release Date:2018/08/22 16:25
-
Vector control cannot be selected unless Pr.862 is set to 1. Only the first motor is supported in the motor setting of FR Configurator2. More Details >>
- No:20840
- Release Date:2018/08/22 16:24
-
It can be used in terms of the specifications. However, it is recommended to update the reactor and inverter at the same time because the DC reactor was manu... More Details >>
- No:21017
- Release Date:2018/08/22 16:25