FAQ


FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-A800
FAQ
Keyword Search
FAQ within [ FREQROL-A800 ]
-
The undervoltage warning of the inverter is judged based on the voltage of the main circuit as follows. Power failure only at the main circuit: Output an und... More Details >>
- No:20853
- Release Date:2018/08/22 16:24
-
It can be used in terms of the specifications. However, it is recommended to update the reactor and inverter at the same time because the DC reactor was manu... More Details >>
- No:21017
- Release Date:2018/08/22 16:25
-
In the FR-A800/F800, the restriction on the wiring length of the shielded cable is eliminated. The wiring length is up to 500 m as is the case with the unshi... More Details >>
- No:21089
- Release Date:2018/08/22 16:25
-
For the FR-A700/F700, the hook is cut off for the wiring due to restrictions on the structure. These restrictions are eliminated for the FR-A800/F800. More Details >>
- No:21051
- Release Date:2018/08/22 16:25
-
The mini B connector is used for connecting with FR Configurator2. A USB memory device can be connected to the A connector (host) to save parameters or trace... More Details >>
- No:21095
- Release Date:2018/08/22 16:25
-
The FR-PU07(BB) can be used with some restrictions.* The major restrictions are as follows. - Pr.1000 or later cannot be set. - Alarms or warnings that are a... More Details >>
- No:21119
- Release Date:2018/08/22 16:26
-
Installation necessity of a DC reactor
A DC reactor connection is required under the following conditions. - Inverter capacity is 75K or higher - Motor capacity is 75 kW or higher. If any of the a... More Details >>
- No:21077
- Release Date:2018/08/22 16:25
-
Parameter copy to the USB memory
No. Writing is not available when the model is different. Writing the parameter copy file using a USB memory device is available only for the same models. Ot... More Details >>
- No:21014
- Release Date:2018/08/22 16:25
-
It can be used since the specifications are the same. Note that the warranty period and expected lifespan for the A700/F700P are inherited. More Details >>
- No:21092
- Release Date:2018/08/22 16:25
-
Frequency search of the FR-A800/FR-F800
DC voltage is applied when Pr.162 = 0, and AC voltage is applied when Pr.162 = 3 or 13. For the AC, the operation is easier to continue than the DC and the i... More Details >>
- No:20831
- Release Date:2018/08/22 16:24
11-20 of Total 142