Start main contents

  • Font Size
  • S
  • M
  • L

FAQ within [ FREQROL-F800 ]

11-20 of Total 89

prev 2 / 9page next
  • FR-PU07

    No. They can be connected with the connection cable (FR-CB20[]). [] indicates cable length (1 m, 3 m, 5 m). More Details >>

    • No:21081
    • Release Date:2018/08/22 16:25
  • FR-A8AX/A8AY

    For the FR-A700/F700, the hook is cut off for the wiring due to restrictions on the structure. These restrictions are eliminated for the FR-A800/F800. More Details >>

    • No:21051
    • Release Date:2018/08/22 16:25
  • MT-BU5

    No, the MT-BU5 is not available Use the FR-BU2 instead. More Details >>

    • No:21076
    • Release Date:2018/08/22 16:25
  • Plug-in options

    The conventional plug-in option (FR-A7[][]) cannot be used. Use the dedicated plug-in option (FR-A8[][]). More Details >>

    • No:21114
    • Release Date:2018/08/22 16:25
  • Copy function

    No. (Using the copy function causes an error.) Use the FR-DU08 when performing the copy function of the operation panel. More Details >>

    • No:21118
    • Release Date:2018/08/22 16:26
  • Parameter copy to the USB memory

    No. Writing is not available when the model is different. Writing the parameter copy file using a USB memory device is available only for the same models. Ot... More Details >>

    • No:21014
    • Release Date:2018/08/22 16:25
  • Frequency search of the FR-A800/FR-F800

    DC voltage is applied when Pr.162 = 0, and AC voltage is applied when Pr.162 = 3 or 13. For the AC, the operation is easier to continue than the DC and the i... More Details >>

    • No:20831
    • Release Date:2018/08/22 16:24
  • Wiring length

    In the FR-A800/F800, the restriction on the wiring length of the shielded cable is eliminated. The wiring length is up to 500 m as is the case with the unshi... More Details >>

    • No:21089
    • Release Date:2018/08/22 16:25
  • Gain adjustment under the speed control

    Since the lower limit has been internally set, 3% or less is recognized as 3%. More Details >>

    • No:21016
    • Release Date:2018/08/22 16:25
  • FR-PA07

    No, it cannot. The standard operation panel (FR-DU08) can be connected to the face of the board by using the FR-ADP (operation panel connection connector) an... More Details >>

    • No:20898
    • Release Date:2018/08/22 16:24

11-20 of Total 89