Setting values of the FR-F800 when re...
The performance and noise countermeasure were improved and the initial value is set to "8". Try with the initial value "2" first. If the noise is distracting... More Details >>
Life measurement of the main circuit ...
No. Turn OFF and ON both main circuit and control circuit. More Details >>
Parameter copy to the USB memory
Yes. Parameters can be read except during an inverter reset or when the password function is set. More Details >>
It is not possible because the RS-485 terminal block is not installed. Use the FR-A800 (RS-485 communication type) when performing the RS-485 communication. More Details >>
Yes, it can like the standard product. More Details >>
No, they do not. Pr.72 is invalid at the offline auto tuning. It is also invalid when the motor rotates with Pr.96 = 101. More Details >>
It can be used since the specifications are the same. Note that the warranty period and expected lifespan for the A700/F700P are inherited. More Details >>
It is available if the option FR-A8TAT (Control circuit terminal block intercompatibility attachment) is installed. (Some functions have restrictions. For th... More Details >>
Installation necessity of a DC reactor
A DC reactor connection is required under the following conditions. - Inverter capacity is 75K or higher - Motor capacity is 75 kW or higher. If any of the a... More Details >>
Parts arrangement is available. Consult with your sales agent. More Details >>