FAQ


FAQAbout Products

- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F800
FAQ
Keyword Search
FAQ within [ FREQROL-F800 ]
-
No, they do not. Pr.72 is invalid at the offline auto tuning. It is also invalid when the motor rotates with Pr.96 = 101. More Details >>
- No:20878
- Release Date:2018/08/22 16:24
-
No. They can be connected with the connection cable (FR-CB20[]). [] indicates cable length (1 m, 3 m, 5 m). More Details >>
- No:21081
- Release Date:2018/08/22 16:25
-
LD is not supported, however, SLD is supported. More Details >>
- No:21054
- Release Date:2018/08/22 16:25
-
They can be compliant by connecting an optional DC reactor (FR-HEL). (A capacitive filter and common mode choke are built in (the common mode choke is provid... More Details >>
- No:21117
- Release Date:2018/08/22 16:26
-
The RJ-45 compatible connector (LAN cable), switching hub, and others are required The auto detection of the connection devices, externally monitoring the in... More Details >>
- No:20882
- Release Date:2018/08/22 16:24
-
Yes, it does, however, it does not acquire the certification of the BACnet association standard. More Details >>
- No:20863
- Release Date:2018/08/22 16:24
-
The maximum values are kept. The values are not cleared to zero. More Details >>
- No:21015
- Release Date:2018/08/22 16:25
-
The direct connection with the inverter like the standard model, and the connection via the GOT and relay station (programmable controller) are available. On... More Details >>
- No:20879
- Release Date:2018/08/22 16:24
-
If using an inverter with capacity of 75K or higher, or motor with capacity of 75 kW or higher, always select and install the inverter based on the capacity ... More Details >>
- No:21112
- Release Date:2018/08/22 16:25
-
Combination of the FR-F800 and MM-EFS
Yes, it can. Set "12" or "112" to the MM-EFS capacity used for Pr.80 (Motor capacity) and Pr.998 (PM parameter initialization). More Details >>
- No:20820
- Release Date:2018/08/22 16:24
21-30 of Total 89