  • FR-F800

    Yes, the current is limited under the PM sensorless control. More Details >>

    • No:20936
    • Release Date:2018/08/22 16:25
  • Output signal

    The length within 30 m is recommended. When the wiring length is long, signals may not be received accurately due to the increased inductance. More Details >>

    • No:20995
    • Release Date:2018/08/22 16:25
  • Combination of the FR-F800 and MM-EFS

    Yes, it can. Set "12" or "112" to the MM-EFS capacity used for Pr.80 (Motor capacity) and Pr.998 (PM parameter initialization). More Details >>

    • No:20820
    • Release Date:2018/08/22 16:24
  • PLC function

    The setting is enabled at the Y24 start-up. The frequency cannot be changed when Y24 is always ON. Turn ON Y24 when writing a frequency. More Details >>

    • No:21048
    • Release Date:2018/08/22 16:25
  • Operation panel

    If the operation panel has not been operated for the time set in Pr.1048 Display-off waiting time, the display-off mode is enabled and the "MON" LED blinks s... More Details >>

    • No:21075
    • Release Date:2018/08/22 16:25
  • Trace data

    The trace data is stored in the built-in RAM of the inverter and deleted when the power is turned OFF or the inverter is reset. The data can be held with any... More Details >>

    • No:21078
    • Release Date:2018/08/22 16:25
  • Load characteristics fault detection

    Only the V/F control is related with Pr.56. The motor torque is calculated from the current value (not Pr.56) and motor constant. For the V/F control, it is ... More Details >>

    • No:20893
    • Release Date:2018/08/22 16:24
  • Load characteristics fault detection

    It is based on the motor rated torque. More Details >>

    • No:20895
    • Release Date:2018/08/22 16:24
  • Residual voltage at the output shutoff

    The rotation speed has almost no effect. The residual voltage increases when the torque boost is increased, but no adjustment is required. More Details >>

    • No:20906
    • Release Date:2018/08/22 16:25
  • FR-F800

    No, it isn't. Use the multiple rating (LD, SLD) of the FR-A800. More Details >>

    • No:20972
    • Release Date:2018/08/22 16:25