  • Load characteristics fault detection

    Only the V/F control is related with Pr.56. The motor torque is calculated from the current value (not Pr.56) and motor constant. For the V/F control, it is ... More Details >>

    • No:20893
    • Release Date:2018/08/22 16:24
  • FR-F800

    Yes, the current is limited under the PM sensorless control. More Details >>

    • No:20936
    • Release Date:2018/08/22 16:25
  • FR-F800

    No, it isn't. Use the multiple rating (LD, SLD) of the FR-A800. More Details >>

    • No:20972
    • Release Date:2018/08/22 16:25
  • Combination of the FR-F800 and MM-EFS

    Yes, it can. Set "12" or "112" to the MM-EFS capacity used for Pr.80 (Motor capacity) and Pr.998 (PM parameter initialization). More Details >>

    • No:20820
    • Release Date:2018/08/22 16:24
  • PLC function

    Vector control: The SM1217 turns ON when the motor rotates even if no forward rotation command is send. Other than vector control: The SM1217 turn ON by forw... More Details >>

    • No:20907
    • Release Date:2018/08/22 16:25
  • Storage area

    The storage areas for the sequence programs and for the parameters of the inverter are different. More Details >>

    • No:20958
    • Release Date:2018/08/22 16:25
  • The number of input terminals

    The number of terminals: There are the same input terminals as F700P and the following terminals (4 points) are added. Safety: SI1, SI2, SIC 24 V power suppl... More Details >>

    • No:21070
    • Release Date:2018/08/22 16:25
  • FR-A800

    No, they do not. Pr.72 is invalid at the offline auto tuning. It is also invalid when the motor rotates with Pr.96 = 101. More Details >>

    • No:20878
    • Release Date:2018/08/22 16:24
  • Load characteristics fault detection

    It is based on the motor rated torque. More Details >>

    • No:20895
    • Release Date:2018/08/22 16:24
  • Carrier frequency automatic reducing function

    The function operates immediately when the current of 85% or higher flows. The limit is canceled when the current becomes 80% or lower. More Details >>

    • No:20903
    • Release Date:2018/08/22 16:25