The inverters FR-A200 and V200 do not support CC-Link. (The FR-A500 series supports CC-Link.) Use the open collector output and relay output card when combin... More Details >>
- No:21504
- Release Date:2018/08/22 16:28
-
Imbalanced input and output side power supplies
1. In general, the input power of the inverter is always larger than the output power because the inverter loss is added to the motor loss. 2. In both of cas... More Details >>
- No:21473
- Release Date:2018/08/22 16:27
-
Replacement of the SF-JR with the SF-PR
Since the SF-PR is more efficient compared to the SF-JR, the resistance will decrease and the load current will increase. Check the following two points when... More Details >>
- No:20949
- Release Date:2018/08/22 16:25
-
You cannot reuse the parameter unit (FR-PU01) for the FREQROL-Z series, the parameter unit (FR-PU02) for the FREQROL-A200 and A100 series, and the parameter ... More Details >>
- No:21654
- Release Date:2018/08/22 16:28
-
Setting the tuning data without tuning makes no difference. The tuning method of the FR-A700 is different from that of V500. Tuning can be performed by setti... More Details >>
- No:21139
- Release Date:2018/08/22 16:26
-
Installation dimensions of the heat sink panel through attachment
The heat sink panel through attachment to the FR-A520-5.5K inverter consist of the top installation frame, bottom installation frame, and upper cover. The to... More Details >>
- No:21520
- Release Date:2018/08/22 16:28
-
How can I calculate the processing torque from the measured power?
You can calculate the torque from the power. From the general equation: Pout = ωn × TT = (Pout × τ)/ωnPout: Measured valueωn: Actual motor shaft angular fre... More Details >>
- No:21475
- Release Date:2018/08/22 16:27
-
Countermeasure against noise on input side
In general, the line noise filter (FR-BLF) is used against the power supply noise. The AC reactor also works. As other countermeasures:- Use a metal conduit ... More Details >>
- No:21517
- Release Date:2018/08/22 16:28
-
Number of inverters that can be connected to a 20 A branch circuit breaker
The basic idea is the same, but the total capacity should be 3.7 kW. (The maximum capacity is also 3.7K.) More Details >>
- No:21508
- Release Date:2018/08/22 16:28
-
You can remove the parameter unit FR-PU02 and install the FR-CU01 there. However, since the interface for the parameter unit is used, the communication speed... More Details >>
- No:21625
- Release Date:2018/08/22 16:28