No load current value of motor
No load current for each power supply voltage is as follows:- Approximately 15.5 A for 200 VAC 60 Hz- Approximately 21.7 A for 220 VAC 60 HzThe current is es... More Details >>
- No:21534
- Release Date:2018/08/22 16:28
-
It is not completely recommended to use F700P because the starting torque at low speed of the hydraulic pump may be larger than that of the normal pump. Sele... More Details >>
- No:21126
- Release Date:2018/08/22 16:26
-
How can I calculate the processing torque from the measured power?
You can calculate the torque from the power. From the general equation: Pout = ωn × TT = (Pout × τ)/ωnPout: Measured valueωn: Actual motor shaft angular fre... More Details >>
- No:21475
- Release Date:2018/08/22 16:27
-
Setting the tuning data without tuning makes no difference. The tuning method of the FR-A700 is different from that of V500. Tuning can be performed by setti... More Details >>
- No:21139
- Release Date:2018/08/22 16:26
-
The constant-torque motor and vector motor are the induction motors, which consist of the stator core, gap, and rotor core. For the constant-torque motor, th... More Details >>
- No:21378
- Release Date:2018/08/22 16:27
-
It is the brake function that consumes the rotational energy by heat and stops the motor immediately by short-circuiting between the motor terminals through ... More Details >>
- No:21066
- Release Date:2018/08/22 16:25
-
Do not carry out a pressure test. As for a megger test, carry out the test with 500 VDC as describes in the Instruction Manual of the inverter. More Details >>
- No:20967
- Release Date:2018/08/22 16:25
-
Which is the recommended digital counter?
We recommend the following digital counter: (Connect it between the terminals FM and SD.) Manufacturer: KOYO ELECTRONICS INDUSTRIES CO., LTD.Model: TC-41 More Details >>
- No:21469
- Release Date:2018/08/22 16:27
-
Number of inverters that can be connected to a 20 A branch circuit breaker
The basic idea is the same, but the total capacity should be 3.7 kW. (The maximum capacity is also 3.7K.) More Details >>
- No:21508
- Release Date:2018/08/22 16:28
-
The setting memo of the parameter list seal is not provided with the FR-A500 Instruction Manual. More Details >>