If Pr 27 is not set, the operation starts at the speed of RL. More Details >>
- No:21123
- Release Date:2018/08/22 16:26
-
If "HOLD" is displayed, the key lock mode enabled. Press the "MODE" key for two seconds. Then, change the setting of Pr.79 to "1". More Details >>
- No:21350
- Release Date:2018/08/22 16:27
-
When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>
- No:21327
- Release Date:2018/08/22 16:27
-
When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>
- No:21284
- Release Date:2018/08/22 16:26
-
It is OK if stations are set as reserved. More Details >>
- No:21868
- Release Date:2018/08/22 16:29
-
When the potentiometer is disconnected and frequency commands cease, the input potential becomes around 0 V.Therefore, the frequency command becomes analog-c... More Details >>
- No:21794
- Release Date:2018/08/22 16:29
-
To use the terminal as voltage input, you need to:- Set Pr.267 (Terminal 4 input selection).- Set the voltage/current input switch on the inverter board.- Se... More Details >>
- No:21771
- Release Date:2018/08/22 16:29
-
Some types are designed for the Chinese market and provide Chinese manuals. (Note that the specifications of these types are partially different from the spe... More Details >>
- No:21479
- Release Date:2018/08/22 16:27
-
Use high-duty brake resistor FR-ABR-2.2K. (Shared with the 1.5K inverter.) More Details >>
- No:21330
- Release Date:2018/08/22 16:27
-
To accept the current signal, the terminals AU (current input selection) and SD must be short-circuited. Check it.Note that this terminal AU is not prepared ... More Details >>
- No:21799
- Release Date:2018/08/22 16:29