Set Pr.3 (Base frequency) and Pr.18 (High speed maximum frequency) to "340 Hz", Pr.19 (Base frequency voltage) to "200 V", Pr.125 (Terminal 2 frequency setti... More Details >>
- No:21789
- Release Date:2018/08/22 16:29
-
Priorities are: Low speed (RL) > Middle speed (RM) > High speed (RH).For example, if the low speed (RL) and middle speed (RM) signals are input simulta... More Details >>
- No:21772
- Release Date:2018/08/22 16:29
-
Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>
- No:21685
- Release Date:2018/08/22 16:28
-
Connecting ammeter to output side
Yes. Use a moving-iron type ammeter. However, if the carrier frequency exceeds 5 kHz, do not use that meter since an overcurrent losses produced in the inter... More Details >>
- No:21681
- Release Date:2018/08/22 16:28
-
For the set frequency 60 Hz, ±6 Hz is applied and thus the up to frequency signal is output between 54 Hz and 66 Hz. During acceleration/deceleration to the ... More Details >>
- No:21348
- Release Date:2018/08/22 16:27
-
For the Instruction Manual "Applied", fill in the request sheet which is included in the last part of the Instruction Manual "Basic", and fax it to the speci... More Details >>
- No:21341
- Release Date:2018/08/22 16:27
-
Check if the input side voltage is equally applied to all three phases. The S phase voltage may be low because the input current flows when the voltage of th... More Details >>
- No:21340
- Release Date:2018/08/22 16:27
-
It is Pr.125 (Terminal 2 frequency setting gain frequency). Adjust the slope with C4 (903) (Terminal 2 frequency setting gain) as necessary. More Details >>
- No:21247
- Release Date:2018/08/22 16:26
-
You can change the terminal 4 to voltage input. (The terminal 4 is set to the current input terminal at the initial setting.)To change the terminal 4 to volt... More Details >>
- No:21787
- Release Date:2018/08/22 16:29
-
You can use the setting dial to set the frequency during operation even if Pr.77 is not set to "2".Setting Pr.77 to "2" allows for changing the parameter set... More Details >>
- No:21786
- Release Date:2018/08/22 16:29