FAQ within [ FREQROL-E700 ]

161-170 of Total 394

prev 17 / 40page next
  • FR-E720

    The following is the amount of heat generated for each capacity:0.1K: 14W  0.2K: 20W  0.4K: 32W  0.75K: 50W1.5K: 80W  2.2K: 100W  3.7K: 160W  5.5K: 290W7.5K:... More Details >>

    • No:21706
    • Release Date:2018/08/22 16:29
  • Terminal CS

    FR-E700, D700, and F700PJ do not have the terminal CS and you can only control automatic restart by setting Pr.57 (Restart coasting time). More Details >>

    • No:21707
    • Release Date:2018/08/22 16:29
  • FR-Configurator

    If the values are already entered in the setting column, performing batch write reflects the setting on the inverter. More Details >>

    • No:21709
    • Release Date:2018/08/22 16:29
  • FR-Configurator

    No. You cannot connect it to multiple inverters.You can only connect a single personal computer to a single inverter via USB. More Details >>

    • No:21710
    • Release Date:2018/08/22 16:29
  • Monitor indicator

    Set Pr.37 (Speed display) to the speed obtained when operating the machine at the frequency set with Pr.505 (Speed setting reference). (For FR-F700/E700/D700... More Details >>

    • No:21716
    • Release Date:2018/08/22 16:29
  • Coasting

    1. Set Pr.162 to "10" (Frequency search at every start).2. You can ignore the setting if the motor excitation current is unknown. More Details >>

    • No:21718
    • Release Date:2018/08/22 16:29
  • Parameter setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) to "50 Hz".Set Pr.1 (Maximum frequency) to "50 Hz". More Details >>

    • No:21720
    • Release Date:2018/08/22 16:29
  • Single-phase 200 V input

    The FR-E720S series and D720S series conform to the single-phase 200 V input specifications. More Details >>

    • No:21723
    • Release Date:2018/08/22 16:29
  • Speed setting

    Use the inverter's calibration parameters Pr.C2/C3, Pr.125/C4 to adjust the bias and gain for each inverter.Connect the wires from the frequency setting pote... More Details >>

    • No:21728
    • Release Date:2018/08/22 16:29
  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29