FAQ within [ FREQROL-E700 ]

171-180 of Total 393

prev 18 / 40page next
  • Base frequency setting value

    Set the rated frequency of the motor used to it.  More Details >>

    • No:21814
    • Release Date:2018/08/22 16:29
  • Connecting ammeter to output side

    Yes. Use a moving-iron type ammeter. However, if the carrier frequency exceeds 5 kHz, do not use that meter since an overcurrent losses produced in the inter... More Details >>

    • No:21681
    • Release Date:2018/08/22 16:28
  • Countermeasure against noises

    Yes. The carrier frequency can be decreased by the setting of Pr.72 (PWM frequency selection). More Details >>

    • No:21338
    • Release Date:2018/08/22 16:27
  • Life diagnosis

    When Pr.259 (Main circuit capacitor life measuring) is set to "1", the life diagnosis is ready. Turning OFF the power supply starts measuring the life of the... More Details >>

    • No:21283
    • Release Date:2018/08/22 16:26
  • Running frequency setting

    Pr.338 is for the communication operation command source at communication operation and specifies the command source to supply the start signal.Pr.339 is for... More Details >>

    • No:21880
    • Release Date:2018/08/22 16:29
  • CC-Link

    Yes. However, write the setting data to the RAM of the inverter.Set RWw1 in the setting value and turn ON the frequency setting command RYD.To continuously s... More Details >>

    • No:21825
    • Release Date:2018/08/22 16:29
  • Electromagnetic contactor

    Turning ON/OFF the output side during operation causes open/close surges that may trigger the protective function (against overcurrent or overvoltage) of the... More Details >>

    • No:21725
    • Release Date:2018/08/22 16:29
  • Network operation

    Yes. With the setting "66", you can choose NET operation when X66 is ON, and external operation when X66 is OFF. More Details >>

    • No:21675
    • Release Date:2018/08/22 16:28
  • Capacity selection

    Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>

    • No:21326
    • Release Date:2018/08/22 16:27
  • Language in FR Configurator

    FR-Configurator (FR-SW3-STUP-WJ) is the Japanese version. FR-Configurator (FR-SW3-SETUP-WE) is the English version. More Details >>

    • No:21308
    • Release Date:2018/08/22 16:26