Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>
- No:21326
- Release Date:2018/08/22 16:27
-
Check that Pr.3 (Base frequency) is set to "200 Hz". Adjust Pr.0 (Torque boost) as necessary. More Details >>
- No:21280
- Release Date:2018/08/22 16:26
-
No, it cannot. More Details >>
- No:21253
- Release Date:2018/08/22 16:26
-
You can set reserved and invalid stations.The Instruction Manual instructs to set consecutive numbers because the master regards an empty number as an error. More Details >>
- No:21905
- Release Date:2018/08/22 16:30
-
Keep Y100D turned ON if you are changing the frequency continuously. More Details >>
- No:21883
- Release Date:2018/08/22 16:29
-
Yes.The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current s... More Details >>
- No:21770
- Release Date:2018/08/22 16:29
-
Set Pr.55 (Frequency monitor reference) to "100 Hz".If the indication of the installed frequency meter does not match the running frequency, use the calibrat... More Details >>
- No:21768
- Release Date:2018/08/22 16:29
-
Since the percent value read by the calibration parameter C7 indicates that the voltage of 10 V is internally detected as 101.0%, use 101.0% as is.If you cha... More Details >>
- No:21740
- Release Date:2018/08/22 16:29
-
Change the value of Pr.18 (High speed maximum frequency).You can set any frequency within the range defined by Pr.18. More Details >>
- No:21737
- Release Date:2018/08/22 16:29
-
Connect the brake resistor to the terminal P and terminal PR. (For the FR-A700-7.5K or lower, remove the jumper of the terminals PR and PX.) Do not remove th... More Details >>
- No:21333
- Release Date:2018/08/22 16:27
171-180 of Total 393