FAQ within [ FREQROL-E700 ]

171-180 of Total 393

prev 18 / 40page next
  • Frequency setting

    You can use the setting dial together with the terminal 4.Set Pr.79 (Operation mode) to "3" (Combined operation mode) and assign the AU signal to an unused t... More Details >>

    • No:21856
    • Release Date:2018/08/22 16:29
  • FR-PA07

    Specific settings are not required, however, when replacing the FR-E500, check that Pr.146 (Built-in potentiometer switchover) is not set to "0". If it is "0... More Details >>

    • No:21363
    • Release Date:2018/08/22 16:27
  • Model selection

    Use the FR-A740. Basically, select the capacity according to the calculation result of "rated inverter output current ? rated motor current × 1.1". More Details >>

    • No:21244
    • Release Date:2018/08/22 16:26
  • Frequency setting

    This is due to specifications that multi-speed selection is prioritized and setting with the setting dial is ignored.The setting dial is effective when multi... More Details >>

    • No:21843
    • Release Date:2018/08/22 16:29
  • Frequency setting

    When the potentiometer is disconnected and frequency commands cease, the input potential becomes around 0 V.Therefore, the frequency command becomes analog-c... More Details >>

    • No:21794
    • Release Date:2018/08/22 16:29
  • FR-Configurator

    If the values are already entered in the setting column, performing batch write reflects the setting on the inverter. More Details >>

    • No:21709
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>

    • No:21909
    • Release Date:2018/08/22 16:30
  • CC-Link

    Set Pr.340 (Communication startup mode selection) to other than "0".Also, set Pr.79 (Operation mode) to "0", "2", or "6".Powering the inverter on automatical... More Details >>

    • No:21903
    • Release Date:2018/08/22 16:30
  • Control terminal

    Yes. (Terminal SDs are connected with each other inside of the inverter.) More Details >>

    • No:21845
    • Release Date:2018/08/22 16:29
  • Frequency setting

    It is not stored in a parameter but memorized as the frequency setting value after acceleration by the acceleration signal.You can also choose whether or not... More Details >>

    • No:21733
    • Release Date:2018/08/22 16:29