Both 200 V class and 400 V class are suitable for use in a circuit capable of delivering not more than 100 kA rms symmetrical amperes, 264 V maximum (528 V f... More Details >>
- No:21358
- Release Date:2018/08/22 16:27
-
1. Yes. 2. Set Pr.17 to "2". 3. If the start signal is ON, the operation continues even the emergency stop is OFF. More Details >>
- No:21359
- Release Date:2018/08/22 16:27
-
1. Yes. 2. The standard set by Pr.56. More Details >>
- No:21669
- Release Date:2018/08/22 16:28
-
Set Pr.338 to "0" (NET) and Pr.339 to "1" or "2". More Details >>
- No:21674
- Release Date:2018/08/22 16:28
-
Use Pr.903 (Frequency setting voltage gain) for setting the FR-E500. For the 700 series, use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (... More Details >>
- No:21689
- Release Date:2018/08/22 16:28
-
The operation command source is automatically transferred to the connected FR-PU07 or FR-PA07. More Details >>
- No:21700
- Release Date:2018/08/22 16:28
-
Not possible.Instead of FR-DU07, use FR-PA07 (or FR-PU07) as an operation panel for FR-E700. More Details >>
- No:21708
- Release Date:2018/08/22 16:29
-
No. You cannot check the accumulated number of rotations on the monitor. More Details >>
- No:21715
- Release Date:2018/08/22 16:29
-
Check if Pr.13 (Starting frequency) is set to higher than 10 Hz.Also check if a signal is input through the terminal MRS. More Details >>
- No:21722
- Release Date:2018/08/22 16:29
-
Set Pr.146 (Built-in potentiometer switching) to "0".This allows for using the potentiometer built in the FR-PA02 to set the frequency.(Set this parameter to... More Details >>
- No:21729
- Release Date:2018/08/22 16:29