FAQ within [ FREQROL-E700 ]

351-360 of Total 394

prev 36 / 40page next
  • Terminals P1 and P

    Removal of the jumper between the terminals P1 and P is not necessary unless you are using the DC reactor.Set Pr.30 = "0" when using the brake unit.Since set... More Details >>

    • No:21921
    • Release Date:2018/08/22 16:30
  • Connection cable of FR-Configurator

    The following USB connectors are available.For FR-A700: USB B connector (B receptacle)For FR-E700: USB Mini-B connector (Mini-B receptacle) Use the USB cable... More Details >>

    • No:21317
    • Release Date:2018/08/22 16:27
  • Parameter display setting

    Normally, Pr.80 and Pr.81 are the parameters that can be changed when the operation is stopped in the PU operation mode. The "Er4" is a mode designation erro... More Details >>

    • No:21335
    • Release Date:2018/08/22 16:27
  • Network operation

    Set Pr.338 to "0" (NET) and Pr.339 to "1" or "2". More Details >>

    • No:21674
    • Release Date:2018/08/22 16:28
  • Tuning

    Check the parameters listed below necessary for tuning again.Pr.9, Pr.71, Pr.80, Pr.81, Pr.83, Pr.84, and Pr.96 More Details >>

    • No:21726
    • Release Date:2018/08/22 16:29
  • Running frequency setting

    Pr.338 is for the communication operation command source at communication operation and specifies the command source to supply the start signal.Pr.339 is for... More Details >>

    • No:21880
    • Release Date:2018/08/22 16:29
  • Input/output voltage

    The output voltage will not be imbalanced when the inverter is used. (Since AC is converted into DC and then into AC, the output voltage is hardly effected f... More Details >>

    • No:21278
    • Release Date:2018/08/22 16:26
  • Start command

    Set Pr.338 (Communication command source) to "0" to give a start command from "NET". Set Pr.339 (Speed command source) to "1" to make a frequency setting fro... More Details >>

    • No:21285
    • Release Date:2018/08/22 16:26
  • Running frequency

    There are two methods to reduce the running frequency variation. 1. Increase the setting value of Pr.74 (Input filter time constant) to reduce the variation.... More Details >>

    • No:21296
    • Release Date:2018/08/22 16:26
  • Operation panel (FR-PA02)

    Set Pr.146 (Built-in potentiometer switching) to "0".This allows for using the potentiometer built in the FR-PA02 to set the frequency.(Set this parameter to... More Details >>