FAQ
FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-E700
FAQ
Keyword Search
FAQ within [ FREQROL-E700 ]
-
Signals input from the terminal 4 are not enabled if the terminal AU is not ON. For an inverter without the terminal AU, assign the AU function to an unused ... More Details >>
- No:21679
- Release Date:2018/08/22 16:28
-
The parameter setting software we provide is the FR Configurator (FR-SW3-SETUP-WJ). You must purchase it to use. Once you purchase the software, you can upgr... More Details >>
- No:21673
- Release Date:2018/08/22 16:28
-
Connecting it causes no problem. More Details >>
- No:21671
- Release Date:2018/08/22 16:28
-
The FR-E700 series is not equipped with the EMC filter. More Details >>
- No:21667
- Release Date:2018/08/22 16:28
-
You cannot use the brake unit FR-BU2 with the FR-E740-1.5K. To use the brake unit, increase the inverter capacity to 2.2K. You can use the brake unit with th... More Details >>
- No:21665
- Release Date:2018/08/22 16:28
-
Some types are designed for the Chinese market and provide Chinese manuals. (Note that the specifications of these types are partially different from the spe... More Details >>
- No:21479
- Release Date:2018/08/22 16:27
-
Operations cannot be enabled separately. You only can disable or enable all the operations. More Details >>
- No:21366
- Release Date:2018/08/22 16:27
-
No, we have no cable 50 cm long. The optional cables 1 m, 3 m, and 5 m long are available. (1 m: FR-CB201, 3 m: FR-CB203, 5 m: FR-CB205) More Details >>
- No:21365
- Release Date:2018/08/22 16:27
-
The adapter is not necessary. Only the dedicated cable FR-CB20□ is required. More Details >>
- No:21362
- Release Date:2018/08/22 16:27
-
The mounting screw is not supplied. The mounting screw is supplied with the operation panel. Open the screw hole according to the dimension. (The M3 screw is... More Details >>
- No:21361
- Release Date:2018/08/22 16:27
351-360 of Total 394