FAQ within [ FREQROL-E700 ]

41-50 of Total 393

prev 5 / 40page next
  • Frequency setting

    Yes, you can set Pr.20 to 20 Hz. More Details >>

    • No:21683
    • Release Date:2018/08/22 16:28
  • Megger test

    When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>

    • No:21327
    • Release Date:2018/08/22 16:27
  • Supported model for FR-Configurator

    The FR-E700 is not supported by FR-SW2-SETUP-WJ. The FR-E700 series are supported by FR-SW3-SETUP-WJ. This software can be downloaded from the Mitsubishi Ele... More Details >>

    • No:21314
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Use Pr.125 (Terminal 2 frequency setting gain frequency).  More Details >>

    • No:21913
    • Release Date:2018/08/22 16:30
  • Output voltage

    Since the output frequency was measured, it is considered that the start signal was input correctly.Check the output voltage on the voltage monitor of the in... More Details >>

    • No:21780
    • Release Date:2018/08/22 16:29
  • Input phase loss

    The FR-E700, D700, F700PJ may activate input phase loss protection "E.ILF" if the phase-to-phase voltage of the power supply has become largely unbalanced. More Details >>

    • No:21339
    • Release Date:2018/08/22 16:27
  • Brake unit

    The resistors cannot be used in combination other than described. Operations of brake units and inverters are not verified. When resistors are used in uncert... More Details >>

    • No:21328
    • Release Date:2018/08/22 16:27
  • Frequency setting

    Since Pr.3 (Base frequency) is a parameter to set the rated motor frequency, setting it to 80 Hz does not increase the frequency.Set this parameter to the ra... More Details >>

    • No:21788
    • Release Date:2018/08/22 16:29
  • Parameter

    Press the "MODE" key on the operation panel several times to display "P.0" and parameter setting screen. Then turn the setting dial to display "C..." screen ... More Details >>

    • No:21336
    • Release Date:2018/08/22 16:27
  • Rotation speed display

    It is not switched. The frequency at the fault saved in the faults history is always displayed in frequency [Hz]. More Details >>

    • No:21180
    • Release Date:2018/08/22 16:26