  • Frequency setting

    The output frequency is not changed by the maximum frequency setting. It can be changed by the following methods. - Set the frequency on the operation panel.... More Details >>

    • No:21347
    • Release Date:2018/08/22 16:27
  • Megger test

    When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>

    • No:21327
    • Release Date:2018/08/22 16:27
  • Frequency setting signal

    Check the AU signal (AU - SD). To use the terminal 4, the AU signal (AU - SD) needs to be turned ON. Turning ON the AU signal (AU - SD) disables the terminal 2. More Details >>

    • No:21267
    • Release Date:2018/08/22 16:26
  • FR-DU07

    Not possible.Instead of FR-DU07, use FR-PA07 (or FR-PU07) as an operation panel for FR-E700. More Details >>

    • No:21708
    • Release Date:2018/08/22 16:29
  • Parameter copy method of FR-Configurator

    The data can be copied to other inverters. 1. Save the parameter of the inverter to be copied with extension "pr3" by using "export". 2. Replace the connecte... More Details >>

    • No:21307
    • Release Date:2018/08/22 16:26
  • External multi-speed setting and multi-speed command

    It depends on the setting of Pr.79 (Operation mode).Pr.79 can be set to "2" or "3".If Pr.79 is "2", it is judged that the multi-speed frequency command was s... More Details >>

    • No:21815
    • Release Date:2018/08/22 16:29
  • Frequency setting

    When using the setting dial to set the frequency, turn the dial and display the frequency. Then, press the "SET" key while the desired value flickers.The fre... More Details >>

    • No:21848
    • Release Date:2018/08/22 16:29
  • Cooling fan

    Pr.244 (Cooling fan operation selection) controls turning ON/OFF of the cooling fan and is initially set to "1". When the inverter is powered ON, the cooling... More Details >>

    • No:21670
    • Release Date:2018/08/22 16:28
  • Parameter

    Press the "MODE" key on the operation panel several times to display "P.0" and parameter setting screen. Then turn the setting dial to display "C..." screen ... More Details >>

    • No:21336
    • Release Date:2018/08/22 16:27
  • Electromagnetic contactor

    It is not recommended to start and stop the inverter with the electromagnetic contactor (MC). This will accelerate the deterioration (due to the inrush curre... More Details >>

    • No:21322
    • Release Date:2018/08/22 16:27