FAQ within [ FREQROL-E700 ]

41-50 of Total 393

prev 5 / 40page next
  • FR-E700

    Use Pr.C24 (Frequency setting voltage gain frequency built-in potentiometer). More Details >>

    • No:21847
    • Release Date:2018/08/22 16:29
  • Wiring length

    The total wiring length is as follows: 100 m + (20 m × 5) = 200m. More Details >>

    • No:21144
    • Release Date:2018/08/22 16:26
  • FR-E720

    The following is the amount of heat generated for each capacity:0.1K: 14W  0.2K: 20W  0.4K: 32W  0.75K: 50W1.5K: 80W  2.2K: 100W  3.7K: 160W  5.5K: 290W7.5K:... More Details >>

    • No:21706
    • Release Date:2018/08/22 16:29
  • Frequency setting

    From the LED, it is considered that the operation mode Pr.79 is set to "3".The PU and EXT LEDs turn ON with this setting.In this state, you cannot change bet... More Details >>

    • No:21741
    • Release Date:2018/08/22 16:29
  • Life diagnosis

    When Pr.259 (Main circuit capacitor life measuring) is set to "1", the life diagnosis is ready. Turning OFF the power supply starts measuring the life of the... More Details >>

    • No:21283
    • Release Date:2018/08/22 16:26
  • Frequency setting

    The frequency can be set to 65 Hz with the initial setting.Check if Pr.1 (Maximum frequency) is set to 60 Hz. More Details >>

    • No:21858
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Normally, any of the PU, EXT, or NET LED turns ON.Check if the parameter unit FR-PU04/FR-PU07 or operation panel FR-PA07 is externally connected to the PU co... More Details >>

    • No:21803
    • Release Date:2018/08/22 16:29
  • Current setting

    Yes.The parameters used when the terminal 4 is used are C5, C6, 126, and C7.Set Pr.C5 (Terminal 4 frequency setting bias frequency) while feeding a current s... More Details >>

    • No:21770
    • Release Date:2018/08/22 16:29
  • Terminal FM meter connection

    Check the connection with the meter.If the terminal FM is connected to the positive terminal and the terminal SD is connected to the negative terminal of the... More Details >>

    • No:21762
    • Release Date:2018/08/22 16:29
  • Electronic thermal O/L relay setting

    When using multiple motors, connect an external thermal for each of them. Set Pr.9 to "0" to disable the function. (When multiple motors are present, it is n... More Details >>

    • No:21676
    • Release Date:2018/08/22 16:28