FAQ
FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-D700
FAQ
Keyword Search
FAQ within [ FREQROL-D700 ]
-
The output voltage will not be imbalanced when the inverter is used. (Since AC is converted into DC and then into AC, the output voltage is hardly effected f... More Details >>
- No:21278
- Release Date:2018/08/22 16:26
-
Set Pr.338 (Communication command source) to "0" to give a start command from "NET". Set Pr.339 (Speed command source) to "1" to make a frequency setting fro... More Details >>
- No:21285
- Release Date:2018/08/22 16:26
-
There are two methods to reduce the running frequency variation. 1. Increase the setting value of Pr.74 (Input filter time constant) to reduce the variation.... More Details >>
- No:21296
- Release Date:2018/08/22 16:26
-
Use two resistors for the high-duty brake resistor FR-ABR-15K. (Connect two resistors of 18 ? in parallel.) More Details >>
- No:21329
- Release Date:2018/08/22 16:27
-
Set Pr.146 (Built-in potentiometer switching) to "0".This allows for using the potentiometer built in the FR-PA02 to set the frequency.(Set this parameter to... More Details >>
- No:21730
- Release Date:2018/08/22 16:29
-
Pr.1 (Maximum frequency) and Pr.18 (Maximum frequency). More Details >>
- No:21744
- Release Date:2018/08/22 16:29
-
Using external potentiometer and multi-speed operation together
You can use an external potentiometer and multi-speed operation together.When an external potentiometer signal input and multi-speed setting occur simultaneo... More Details >>
- No:21920
- Release Date:2018/08/22 16:30
-
Configure the same setting as the SF-HRCA. Configure the same setting as the SF-HRCA. A700, E700, D700, F700PJ: Pr.71 = 50F700P, F700: Pr.71 = 1 (Reference) ... More Details >>
- No:21136
- Release Date:2018/08/22 16:26
-
Set Pr.146 (Built-in potentiometer switching) to "0".This allows for using the potentiometer built in the FR-PA02 to set the frequency.(Set this parameter to... More Details >>
- No:21729
- Release Date:2018/08/22 16:29
-
Normally, the inverter starts up in the NET operation mode at power ON when Pr.340 is set to "10" and Pr.79 is set to "0". When it starts up in the PU operat... More Details >>
- No:21319
- Release Date:2018/08/22 16:27