- FAQ > Drive Products > Inverters-FREQROL > FREQROL-D700
FAQ
Keyword Search
FAQ within [ FREQROL-D700 ]
-
When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>
- No:21327
- Release Date:2018/08/22 16:27
-
When using the setting dial to set the frequency, turn the dial and press the "SET" key while the desired value flickers. (The value and "F" flicker alternat... More Details >>
- No:21692
- Release Date:2018/08/22 16:28
-
Change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode). More Details >>
- No:21792
- Release Date:2018/08/22 16:29
-
You cannot use the setting dial while the terminals JOG and SD are turned ON.When performing JOG operation using external signals, set Pr.79 (Operation mode)... More Details >>
- No:21823
- Release Date:2018/08/22 16:29
-
Switching between External operation mode and PU operation mode
Assign X16 signal, and set Pr.79 to "0", to switch the operation mode with turning ON/OFF X16 signal. More Details >>
- No:21288
- Release Date:2018/08/22 16:26
-
The FR-E700, D700, F700PJ may activate input phase loss protection "E.ILF" if the phase-to-phase voltage of the power supply has become largely unbalanced. More Details >>
- No:21339
- Release Date:2018/08/22 16:27
-
1. For MRS, coasting starts when the MRS contact turns ON. For Pr.250 = "0",IM is coasting immediately when the start signal is turned OFF. 2. No. Set eithe... More Details >>
- No:21360
- Release Date:2018/08/22 16:27
-
Calibrate C6 (Pr.904) (Terminal 4 frequency setting bias frequency) and C7 (Pr.905) (Terminal 4 frequency setting gain frequency). If the situation does not ... More Details >>
- No:21265
- Release Date:2018/08/22 16:26
-
It is said that the EEPROM has a lifetime of 100,000 write cycles. When the data is written every time the frequency changes, the life of the EEPROM may not ... More Details >>
- No:20996
- Release Date:2018/08/22 16:25
-
Auto tuning can be performed because the motor is one rank lower than the inverter capacity. More Details >>
- No:21351
- Release Date:2018/08/22 16:27