FAQ within [ FREQROL-D700 ]
-
When the frequency is set using the setting dial, it is not necessary to set it again.The inverter memorizes the setting value internally even after the powe... More Details >>
- No:21842
- Release Date:2018/08/22 16:29
-
External multi-speed setting and multi-speed command
It depends on the setting of Pr.79 (Operation mode).Pr.79 can be set to "2" or "3".If Pr.79 is "2", it is judged that the multi-speed frequency command was s... More Details >>
- No:21815
- Release Date:2018/08/22 16:29
-
The inverter outputs the peak voltage 300 to 400 VDC of the bus voltage not in a pure sine wave but a in a PWM waveform. Check if the lamp to be connected ca... More Details >>
- No:21323
- Release Date:2018/08/22 16:27
-
If Pr.79 = 3, PU and EXT turn ON. Switching between PU and EXT is not available. Turn the setting dial to set the frequency and press the SET key to accept it. More Details >>
- No:21695
- Release Date:2018/08/22 16:28
-
When carrying out the megger test of the inverter, shorten all the terminals R, S, T, U, V, and W of the main circuit and use the 500 VDC megger for earth. D... More Details >>
- No:21327
- Release Date:2018/08/22 16:27
-
Switching between External operation mode and PU operation mode
Assign X16 signal, and set Pr.79 to "0", to switch the operation mode with turning ON/OFF X16 signal. More Details >>
- No:21288
- Release Date:2018/08/22 16:26
-
Set Pr.37 (Speed display) to the speed obtained when operating the machine at the frequency set with Pr.505 (Speed setting reference). (For FR-F700/E700/D700... More Details >>
- No:21716
- Release Date:2018/08/22 16:29
-
Adjust the terminal 2 bias with Pr.C2 and Pr.C3, and the terminal 2 gain with Pr.125 and Pr.C4. Set Pr.C2 (Terminal 2 frequency setting bias frequency) to 20... More Details >>
- No:21685
- Release Date:2018/08/22 16:28
-
Saving parameter with FR-Configurator
When FR Configurator (FR-SW3-SETUP-WJ) is saved as a file from the menu, the extension is "me3". The size of this fie will be large since device settings and... More Details >>
- No:21311
- Release Date:2018/08/22 16:26
-
The output voltage will not be imbalanced when the inverter is used. (Since AC is converted into DC and then into AC, the output voltage is hardly effected f... More Details >>
- No:21278
- Release Date:2018/08/22 16:26