  • 10 VDC voltage from terminal 10

    Setting Pr.73 to "0" does not generate 10 VDC output.The inverter itself only has 5 V at the terminal 10.Setting this parameter to "0" allows 10 V input betw... More Details >>

    • No:21727
    • Release Date:2018/08/22 16:29
  • Using external potentiometer and multi-speed operation together

    You can use an external potentiometer and multi-speed operation together.When an external potentiometer signal input and multi-speed setting occur simultaneo... More Details >>

    • No:21920
    • Release Date:2018/08/22 16:30
  • Frequency

    When the torque is supposed as 100% at 60 Hz, the torque becomes 75 % at 80 Hz. (Under V/F control, the torque decreases when the frequency exceeds 60 Hz bec... More Details >>

    • No:21284
    • Release Date:2018/08/22 16:26
  • Frequency meter

    First, check if Pr.55 (Frequency monitor reference) that is the reference for the FM output is set correctly.Next, operate the inverter (without connecting a... More Details >>

    • No:21808
    • Release Date:2018/08/22 16:29
  • Brake resistor

    Use two resistors for the high-duty brake resistor FR-ABR-15K. (Connect two resistors of 18 ? in parallel.) More Details >>

    • No:21329
    • Release Date:2018/08/22 16:27
  • MRS setting

    1. For MRS, coasting starts when the MRS contact turns ON. For Pr.250 = "0",IM is coasting immediately when the start signal is turned OFF.  2. No. Set eithe... More Details >>

    • No:21360
    • Release Date:2018/08/22 16:27
  • External operation

    The inverter has the calibration function.Use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (Terminal 2 frequency setting gain) for calibrat... More Details >>

    • No:21849
    • Release Date:2018/08/22 16:29
  • Operation panel

    This is because the protective function works to stop the motor. It is not a fault indication.To cancel the protective function, turn OFF the start signal an... More Details >>

    • No:21775
    • Release Date:2018/08/22 16:29
  • RS-485 communication

    Blinking of the "RUN" LED on the panel suggests that the frequency command may not be input. Create a frequency setting data as for the forward rotation comm... More Details >>

    • No:21301
    • Release Date:2018/08/22 16:26
  • Frequency setting

    If Pr.79 (Operation mode) is set to "0" (PU/EXT switching mode), press the PU/EXT button on the operation panel to turn on the PU LED.Turn the setting dial t... More Details >>

    • No:21855
    • Release Date:2018/08/22 16:29