To enable the frequency setting with the setting dial and multi-speed setting, set Pr.79 to "3". Note that multi-speed setting is prioritized over setting us... More Details >>
The operation panels of the FR-E700, FR-D700, and FR-F700PJ are not detachable.Therefore, it cannot be attached to the enclosure surface.You can use the opti... More Details >>
The inverter has the calibration function.Use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (Terminal 2 frequency setting gain) for calibrat... More Details >>
When using the setting dial to set the frequency, turn the dial and display the frequency. Then, press the "SET" key while the desired value flickers.The fre... More Details >>
Yes. You can use the setting dial of the inverter to set the frequency as well as change the parameter values. More Details >>
Yes. (Terminal SDs are connected with each other inside of the inverter.) More Details >>
You also need to set Pr.79 (Operation mode) to "3". More Details >>
This is due to specifications that multi-speed selection is prioritized and setting with the setting dial is ignored.The setting dial is effective when multi... More Details >>
When the frequency is set using the setting dial, it is not necessary to set it again.The inverter memorizes the setting value internally even after the powe... More Details >>
Since the operation panels of the E700, D700, and F700PJ do not have keys for the forward (FWD) and reverse (REV) rotations, you can only command rotation in... More Details >>