FAQ within [ FREQROL-A700 ]

101-110 of Total 352

prev 11 / 36page next
  • CC-Link

    Set Pr.340 (Communication startup mode selection) to other than "0".Also, set Pr.79 (Operation mode) to "0", "2", or "6".Powering the inverter on automatical... More Details >>

    • No:21903
    • Release Date:2018/08/22 16:30
  • Frequency setting

    Since Pr.125 (Terminal 2 frequency setting gain frequency) is initially set to 60 Hz, change it to 85 Hz. More Details >>

    • No:21907
    • Release Date:2018/08/22 16:30
  • Frequency setting

    Set Pr.125 (Terminal 2 frequency setting gain frequency) = "90 Hz".This changes the frequency with the potentiometer turned to the maximum position (at 5 V i... More Details >>

    • No:21909
    • Release Date:2018/08/22 16:30
  • Frequency setting

    You can connect up to three inverters to a single external frequency setting potentiometer to control them.   More Details >>

    • No:21917
    • Release Date:2018/08/22 16:30
  • Input phase loss protection

    The initial value of Pr.872 is set to "1" (Valid) because the A701 have regeneration unit built-in and an overvoltage may occur when the regenerative operati... More Details >>

    • No:20945
    • Release Date:2018/08/22 16:25
  • FR-A800

    No. Check the parameter setting of the A700, and then adjust the parameter setting of the A800 to those of the A700. For the details, refer to the replacemen... More Details >>

    • No:21107
    • Release Date:2018/08/22 16:25
  • Fast-response current limit

    It is not activated because the function itself is disabled. More Details >>

    • No:21137
    • Release Date:2018/08/22 16:26
  • Rotation speed display

    It is not switched. The frequency at the fault saved in the faults history is always displayed in frequency [Hz]. More Details >>

    • No:21180
    • Release Date:2018/08/22 16:26
  • Electronic bypass function

    For countermeasures against the open/close surge of the MC (magnetic contactor). Insert a diode not to apply 27 VDC or more to the open collector terminal of... More Details >>

    • No:21188
    • Release Date:2018/08/22 16:26
  • Electronic bypass function

    Turn ON and OFF the RES signal to enable the inverter-driven operation. More Details >>

    • No:21190
    • Release Date:2018/08/22 16:26