  • Frequency setting

    Check the setting of Pr.79 (Operation mode).If the setting value is "2", frequency commands from an external terminal is effective and the frequency setting ... More Details >>

    • No:21797
    • Release Date:2018/08/22 16:29
  • Frequency setting

    To accept the current signal, the terminals AU (current input selection) and SD must be short-circuited. Check it.Note that this terminal AU is not prepared ... More Details >>

    • No:21799
    • Release Date:2018/08/22 16:29
  • Frequency setting

    When running the inverter in Advanced magnetic flux vector control, the frequency setting value is increased by the amount of the motor's slippage, resulting... More Details >>

    • No:21801
    • Release Date:2018/08/22 16:29
  • External multi-speed setting and multi-speed command

    It depends on the setting of Pr.79 (Operation mode).Pr.79 can be set to "2" or "3".If Pr.79 is "2", it is judged that the multi-speed frequency command was s... More Details >>

    • No:21815
    • Release Date:2018/08/22 16:29
  • Operation mode setting value

    Set Pr.79 to "2" (external operation mode).    More Details >>

    • No:21818
    • Release Date:2018/08/22 16:29
  • Operation stop, frequency setting

    Set Pr.79 (Operation mode) to "1" (PU operation mode).  More Details >>

    • No:21819
    • Release Date:2018/08/22 16:29
  • Running frequency

    Check the setting of Pr.1 (Maximum frequency) and Pr.18 (High speed maximum frequency).Pr.1 is initially set to "120 Hz". More Details >>

    • No:21821
    • Release Date:2018/08/22 16:29
  • CC-Link

    The start commands cannot be input from both sources simultaneously because the operation command source is specified.You can switch the command source as ne... More Details >>

    • No:21828
    • Release Date:2018/08/22 16:29
  • CC-Link

    Slow blinking of the RUN LED indicates reverse operation.Fast blinking indicates that while the start command is input, the running frequency command is not ... More Details >>

    • No:21833
    • Release Date:2018/08/22 16:29
  • Operation mode setting

    Rapid blinking of the RUN LED indicates that the frequency setting command has not been input or the output stop signal has been input.Since Pr.79 is set to ... More Details >>

    • No:21853
    • Release Date:2018/08/22 16:29