  • PU operation

    The relationship between the acceleration/deceleration reference frequency and acceleration/deceleration time does not change between the PU operation and ex... More Details >>

    • No:21694
    • Release Date:2018/08/22 16:28
  • Motor: SF-HJCA

    Configure the same setting as the SF-HRCA. Configure the same setting as the SF-HRCA. A700, E700, D700, F700PJ: Pr.71 = 50F700P, F700: Pr.71 = 1 (Reference) ... More Details >>

    • No:21136
    • Release Date:2018/08/22 16:26
  • Frequency setting

    Up to 30 m. (To avoid noise and voltage drop)   More Details >>

    • No:21910
    • Release Date:2018/08/22 16:30
  • FR-RC

    Pr.30 = "1" and Pr.70 = "0". More Details >>

    • No:21143
    • Release Date:2018/08/22 16:26
  • FR-DU07

    Not possible.Instead of FR-DU07, use FR-PA07 (or FR-PU07) as an operation panel for FR-E700. More Details >>

    • No:21708
    • Release Date:2018/08/22 16:29
  • Multi-speed setting and external potentiometer

    The multi-speed setting is prioritized.The external potentiometer setting is effective when the multi-speed signal is not input. More Details >>

    • No:21773
    • Release Date:2018/08/22 16:29
  • MRS setting

    1. For MRS, coasting starts when the MRS contact turns ON. For Pr.250 = "0",IM is coasting immediately when the start signal is turned OFF.  2. No. Set eithe... More Details >>

    • No:21360
    • Release Date:2018/08/22 16:27
  • Multi-speed setting

    If Pr 27 is not set, the operation starts at the speed of RL. More Details >>

    • No:21123
    • Release Date:2018/08/22 16:26
  • Frequency setting

    For the set frequency 60 Hz, ±6 Hz is applied and thus the up to frequency signal is output between 54 Hz and 66 Hz. During acceleration/deceleration to the ... More Details >>

    • No:21348
    • Release Date:2018/08/22 16:27
  • JOG function

    When Pr.79 is set to "3", the JOG operation is not available by turning ON the terminal JOG.Instead of the JOG function, you can set the low-speed RL of the ... More Details >>

    • No:21760