FAQ
FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-F700
FAQ
Keyword Search
FAQ within [ FREQROL-F700 ]
-
Automatic restart after instantaneous power failure
The inverter restart operation is disabled at turn-OFF of the CS signal while a value other than "9999" (with restart) is set in Pr.57. The terminals CS and ... More Details >>
- No:21255
- Release Date:2018/08/22 16:26
-
Set C5 (Pr.904) (Terminal 4 frequency setting bias frequency) to 0 Hz and Pr.126 (Terminal 4 frequency setting gain frequency) to 50 Hz. More Details >>
- No:21268
- Release Date:2018/08/22 16:26
-
Yes. The single-phase 200 V can be input. If the single-phase input is performed when Pr.872 (Input phase loss protection) is set to "1", the input phase los... More Details >>
- No:21270
- Release Date:2018/08/22 16:26
-
Check that Pr.3 (Base frequency) is set to "200 Hz". Adjust Pr.0 (Torque boost) as necessary. More Details >>
- No:21280
- Release Date:2018/08/22 16:26
-
When Pr.259 (Main circuit capacitor life measuring) is set to "1", the life diagnosis is ready. Turning OFF the power supply starts measuring the life of the... More Details >>
- No:21283
- Release Date:2018/08/22 16:26
-
FR-Configurator (FR-SW3-STUP-WJ) is the Japanese version. FR-Configurator (FR-SW3-SETUP-WE) is the English version. More Details >>
- No:21308
- Release Date:2018/08/22 16:26
-
Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>
- No:21326
- Release Date:2018/08/22 16:27
-
Check if the input side voltage is equally applied to all three phases. The S phase voltage may be low because the input current flows when the voltage of th... More Details >>
- No:21340
- Release Date:2018/08/22 16:27
-
For the set frequency 60 Hz, ±6 Hz is applied and thus the up to frequency signal is output between 54 Hz and 66 Hz. During acceleration/deceleration to the ... More Details >>
- No:21348
- Release Date:2018/08/22 16:27
-
If "HOLD" is displayed, the key lock mode enabled. Press the "MODE" key for two seconds. Then, change the setting of Pr.79 to "1". More Details >>
- No:21350
- Release Date:2018/08/22 16:27
211-220 of Total 296